Carrier 48/50PD05 Air Conditioner User Manual


 
56
Scrolling Marquee Display
This device is the keypad interface used to access rooftop
information, read sensor values, and test the unit. (See Fig. 23.)
The Scrolling M arquee display is a 4-key, 4-character, 16-segment
LED (light-emitting diode) display. Eleven mode LEDs are located
on the display as well as an Alarm Status LED. See Basic Control
Usage section for further details.
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ENTER
MODE
ESCAPE
C06320
Fig. 23 -- Sc rolling Marquee
Accessory Navigatort Display
The accessory hand-held Navigator display can be used with
48/50PD units. (See Fig. 24.) The Navigator display operates the
same way as the Scrolling Marquee device. The Navigator display
plugs into the LEN port on either TB or the ECB board.
Ru
n Sta
tu
s
S
e
rv
ice
Te
s
t
T
em
p
era
ture
s
P
res
s
ure
s
S
e
tpo
in
ts
In
pu
ts
O
utp
uts
C
on
fig
u
ra
tion
T
im
e C
lo
ck
O
p
er
ating
M
od
es
A
la
rm
s
E
N
T
E
R
E
S
C
M
O
D
E
Ala
rm
Sta
tus
T
IM
E
E
W
T
L
W
T
S
E
T
P
1
2
.
5
8
5
4
.
6
°
F
4
4
.1
°
F
4
4
.
0
°
F
N
A
V
I
G
A
T
O
R
C
o
m
f
o
r
t
L
in
k
C06321
Fig. 24 -- Accessory Navigatort Display
Carrier Comfort Network (CCN)R Interface
The units can be connected to the CCN if desired. The
communication bus wiring is a shielded, 3-conductor cable with
drain wire and is field supplied and installed. The system elements
are connected to the communication bus in a daisy chain
arrangement. (See Fig. 25.) The positive pin of each system
element communication connector must be wired to the positive
pins of the system elements on either side of it. This is also
required for the negative and signal ground pins of each system
element. Wiring connections for CCN should be made at TB. (See
Fig. 25.) Consult the CCN Contractor’s Manual for further
information.
IMPORTANT: Conductors and drain wire must be 20 AWG
(American Wire Gauge) minimum stranded, tinned copper.
Individual conductors must be insulated with PVC, PVC/nylon,
vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of --20_Cto
60_C is required. See Table below for acceptable wiring.
MANUFACTURER PART NO.
Alpha
2413 or 5463
Belden
8772
Carol
C2528
West Penn
302
It is important when connecting to a CCN communication bus that
a color-coding scheme be used for the entire network to simplify
the installation. It is recommended that red be used for the signal
positive, black for the signal negative and white for the signal
ground. Use a similar scheme for cables containing different
colored wires.
At each system element, the shields of its communication bus
cables must be tied together. The shield screw on TB1 can be used
to tie the cables together . If the communication bus is entirely
within one building, the resulting continuous shield must be
connected to a ground at one point only. The shield screw on TB1
is not acceptable for grounding. If the communication bus cable
exits from one building and enters another, the shields must be
connected to grounds at the lightning suppressor in each building
where the cable enters or exits the building ( one point per building
only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the r ed (+), white
(ground), and black (--) conductors. (Substitute appropriate
colors for dif ferent colored cables.)
3. Connect the red wire to (+) terminal on TB1, the white wire
to COM terminal, and the black wire to the (--) terminal.
4. The RJ14 CCN connector on TB1 can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Carrier network software).
5. Restore power to unit.
IMPORTANT: A shorted CCN bus cable will prevent some
routines from running and may prevent the unit from starting. If
abnormal conditions occur, unplug the connector. If conditions
return to normal, check the CCN connector and cable. Run new
cable if necessary . A short in one section of the bus can cause
problems with all system elements on the bus.
Field-Installed Accessories
Space Temperature Sensor (T--55)
The T--55 space temperature sensor (part no. 33ZCT55SPT) is a
field-installed accessory . The sensor is installed on a building
interior wall to measure room air temperature. The T--55 sensor
also includes an override button on the front cover to permit
occupants to override the Unoccupied Schedule (if programmed).
TB1-- T55--1 Sensor Input........
TB1 --T55--2 Sensor Common........
Space Temperature Sensor (T--56)
The T--56 space temperature sensor (part no. 33ZCT56SPT) is a
field-installed accessory . This sensor includes a sliding scale on the
front cover that permits an occupant to adjust the space temperature
set point remotely. The T --56 sensor also includes an override
button on the front cover to allow occupants to override the
unoccupied schedule (if programmed).
TB1-- T55--1 Sensor Input........
TB1 --T55--2 Sensor Common........
TB1-- T55 -- 3 Setpoint Offset Input........
48/50PD