APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 34 — MODE - CONFIGURATION
ITEM EXPANSION RANGE UNITS DEFAULT
CCN
TABLE/SUB---TABLE
CCN POINT
PAGE
NO.
CONFIGURATION SERVICE
CONFIGURATION
DISP Display Configuration DISPLAY
METR Metric Display On/Off Off DISPUNIT 11
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE 11
PROT Password Enable Enable/Disable Disable PASS_EBL 12
PSWD Service Password 0000 to 9999 1111 PASSWORD 12
TEST Test Display LEDs On/Off Off (display only, not in
table)
DISPTEST 12
UNIT Unit Configuration UNIT
S.DLY Startup Delay 0 to 600 sec 30 STARTDLY 12
OC.FN FanOnWhenOccupied Yes/No Yes OCC_FAN 12
IDF.F Shut Down on IDF Failure Yes/No Yes FATALFAN 12
FS.MX Supply Fan Maximum
Speed
80 to 100 % 100 SPEEDMAX 12
FS.MN Supply Fan Minimum
Speed
10 to 40 % 20 SPEEDMIN 12
FS.VM Vent Mode Fan Speed 40 to 100 ^F 50 SPEEDVNT 12
FN.SW Fan Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
FANSTCFG 12
FL.SW Filter Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
FILSTCFG 12
FS.SW Fire Shutdown Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG 12
RM.SW Remote Occupancy
Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG 12
RH.S RH Sensor on OAQ Input Yes/No No RH_OAQ 13
RH.SW Space Humidity Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 HUMSTCFG 13
TCS.C Temp Cmp Strt Cool Factr 0to60 mins 0 TCSTCOOL 13
TCS.H TempCmpStrtHeatFactr 0to60 mins 0 TCSTHEAT 13
COOL Cooling Configuration COOL_CFG
MIN.C Min Compressor Capacity 15 to 80 % 70 MIN_CAPC 14
FS.CD Fan Speed Control
Demand
1to9.9 ^F 3 SPEEDDMD 17
MRT.C Compressor Min On Time 120 to 999 sec 180 MIN_ON
MOT.C Compressor Min Off Time 300 to 999 sec 300 MIN_OFF
RST.C Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S 24
FOD.C Fan-off Delay, Mech Cool 0 to 600 sec 60 COOL_FOD
CS.A1 Current Sensing A1 Enable/Disable Disable: reserved for
future use
DO NOT ENABLE
A1_SENSE 25
C.LO Compressor Lockout
Temp
0 to 100F dF 0 OATLCOMP
ALM.N Alert Each Strike Yes//No Yes ALM_NOW 24
SAT Supply Air Temperature
SASP Cool Supply Air Setpoint 45 to 75 dF 65 SASP 17
SA.MU SASP Maximum Reset Up 0to20 ^F 10 SASPMAXU 18
SA.MD SASP Maximum Reset
Down
--- 20 to 0 ^F --- 10 SASPMAXD 18
SAT.U Minimum SAT Upper Level 35.0 to 65.0 dF 60 SATMIN_H
SAT.L MinimumSAT Lower Level 35.0 to 65.0 dF 45 SATMIN_L
SST Low Suction Control
SST.O Suction OK Temperature 10 to 50 dF 18 SSTOK 26
SST.1 Low Suction --- Level 1 10 to 50 dF 20 SSTLEV1 26
SST.2 Low Suction --- Level 2 5to50 dF 15 SSTLEV2 26
SST.3 Low Suction --- Level 3 0to50 dF 10 SSTLEV3 26
PSI.D Ckt A Minimum Pressure 0 to 500 psig 20 DELTAP_A 26
OFC OutdoorFan Control
1.MXP FanLev1 Max Pressure 100 to 500 psig 450 LEV1MAXP 15
2.MNP Fan Lev2 Min Pressure 100 to 500 psig 200 LEV2MINP 15
2.ON FanLev2OnTemperature 0 to 100 F 55 LEV2ON 15
2.OFF Fan Lev2 Off Temperature 0 to 100 F 45 LEV2OFF 15
48/50PD