Table 13 Keyboard Directory (cont)
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
AIRQUAL1
Configuration of indoor air quality
and AQ sensor no. 1
MPG X Master proportional gain
MIG X Master integral gain
XDP X Maximum damper position
Q1LV X
Air quality sensor 1 low voltage
point
Q1HV X
Air quality sensor 1 high voltage
point
Q1LR X
Air quality sensor 1 low voltage
reference
Q1HR X
Air quality sensor 1 high voltage
reference
MDP X Minimum damper position
AIRQUAL2
Configuration of indoor air quality
and AQ sensor no. 2
MPG X Master proportional gain
MIG X Master integral gain
XDP X Maximum damper position
Q2LV X Air quality sensor 2 low voltage point
Q2HV X Air quality sensor 2 high voltage point
Q2LR X Air quality sensor 2 low voltage reference
Q2HR X Air quality sensor 2 high voltage reference
MDP X Minimum damper position
AOSS X Configuration of optimal start/stop
BLDF X Building factor
UOCF X 24 hour occupied factor
SETB X Set point bias
OSMT X Maximum allowable stop time
SPRESET Configuration of space temperature reset
RTIO X Reset ratio X
LIMT X Reset limit X
LOADSHED Configuration of loadshed
LSGP X Loadshed group number (1-16)
FANTRACK Configuration of fan tracking
SVUL X Supply velocity upper limit
RVUL X Return velocity upper limit
SDAR X Supply duct area
RDAR X Return duct area
MPG X Master proportional gain
MIG X Master integral gain
MDG X Master derivative gain
SMG X Submaster gain
SCV X Submaster center value
SMR X Submaster reference value
SMR X Submaster reference value forced
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
HUMIDITY Configuration of humidity
MPG X Master proportional gain
MIG X Master integral gain
MDG X Master derivative gain
SMG X Submaster gain
SCV X Submaster center value
SMR X Submaster reference value
SMR X Submaster reference value forced
ALRMLIMT Configuration of alarm limits
SPLO X
Space temperature low alarm limit/
occupied
SPHO X
Space temperature high alarm limit/
occupied
SPLU X
Space temperature low alarm limit/
unoccupied
SPHU X
Space temperature high alarm limit/
unoccupied
SALO X
Supply air temperature low alarm limit/
occupied
SAHO X
Supply air temperature high alarm limit/
occupied
SALU X
Supply air temperature low alarm limit/
unoccupied
SAHU X
Supply air temperature high alarm limit/
unoccupied
RALO X
Return air temperature low alarm limit/
occupied
RAHO X
Return air temperature high alarm limit/
occupied
RALU X
Return air temperature low alarm limit/
unoccupied
RAHU X
Return air temperature high alarm limit/
unoccupied
TLO X
Temperature input low alarm limit/
occupied
THO X
Temperature input high alarm limit/
occupied
TLU X
Temperature input low alarm limit/
unoccupied
THU X
Temperature input high alarm limit/
unoccupied
OATL X Outside air temperature low alarm limit
OATH X Outside air temperature high alarm limit
MATL X Mixed air temperature low alarm limit
MATH X Mixed air temperature high alarm limit
RHL X Relative humidity low alarm limit
RHH X Relative humidity high alarm limit
ORHL X
Outside air relative humidity low alarm
limit
ORHH X
Outside air relative humidity high alarm
limit
SPL X Static pressure low alarm limit
SPH X Static pressure high alarm limit
SVPL X Supply velocity pressure low alarm limit
SVPH X Supply velocity pressure high alarm limit
RVPL X Return velocity pressure low alarm limit
RVPH X Return velocity pressure high alarm limit
CFML X Delta CFM x 100 low alarm limit
CFMH X Delta CFM x 100 high alarm limit
Q1H X Air quality sensor 1 high alarm limit
Q2H X Air quality sensor 2 high alarm limit
74