Carrier 39L Air Conditioner User Manual


 
Table 1 Input and Output Points
MODULE,
DEFAULT ADDRESS
INPUT
INPUT
TYPE
CHANNEL
NUMBER
OUTPUT
OUTPUT
TYPE
CHANNEL
NUMBER
PSIO (Processor)
ADDRESS 1
SAT AI 1 IGV* AO 13
OAT AI 2 MIXD AO, DO† 14
MAT AI 3 HWC AO 15
RH AI 4 CWC AO 16
LTT DI 5 SF DO 17
SPT AI 6 HIR* DO 18
RAT AI 7
SP* AI 8
AFS DI 9
FLTS DI 10
OARH AI 11
ENT DI 12
PSIO (Option)
ADDRESS 31
SVP* AI 31 RFVC* AO 43
RVP* AI 32 HUM1 AO, DO 44
DHH DI 33 HUM2 DO 45
TEMP AI 34 AOTC AO 46
PRES DI 35 DOTC DO 47
EVAC DI 36 DTCC DO 48
PURG DI 37
FSD DI 38
AQ1 AI 39
AQ2 AI 40
OAVP* AI 41
METER DI 42
DSIO (Electric Heat)
ADDRESS 19
EHS1 DO 23
EHS2 DO 24
EHS3 DO 25
EHS4 DO 26
EHS5 DO 27
EHS6 DO 28
EHS7 DO 29
EHS8 DO 30
DSIO (DX without
Electric Heat)
ADDRESS 19
CUST DI 19 DXS1 DO 23
DXSD DI 20 DXS2 DO 24
DXS3 DO 25
DXS4 DO 26
DXS5 DO 27
DXS6 DO 28
DXS7 DO 29
DXS8 DO 30
DSIO (DX with
Electric Heat)
ADDRESS 49
CUST DI 49 DXS1 DO 53
DXSD DI 50 DXS2 DO 54
DXS3 DO 55
DXS4 DO 56
DXS5 DO 57
DXS6 DO 58
DXS7 DO 59
DXS8 DO 60
LEGEND
AFS Airflow Switch (Supply Fan
Status Switch)
AI Analog Input
AO Analog Output
AOTC Analog Output Temperature
Control
AQ1, 2 Air Quality Sensors 1, 2
CUST Condensing Unit Status
(Outdoor Air Thermostat)
CWC Chilled Water Coil
DI Discrete Input
DHH Duct High Humidity
DO Discrete Output
DOTC Discrete Output Temperature
Control
DTCC Discrete Output Timeclock
Control
DXS1-8 Direct Expansion Cooling
Stages 1-8
DXSD Direct Expansion Cooling
Shutdown
EHS1-8 Electric Heater Stages 1-8
ENT Enthalpy Switch
EVAC Evacuation
FLTS Filter Status Switch
FSD Fire Shutdown
HIR Heat Interlock Relay
HWC Hot Water Coil
HUM1, 2 Humidity Stages 1, 2
IGV Inlet Guide Vanes
LTT Low Temperature Thermostat
(also labelled FRZ)
MAT Mixed-Air Temperature
METER Meter (Pulsed Dry-Contact
Input)
MIXD Mixed-Air Dampers
OARH Outdoor-Air Relative Humidity
OAT Outdoor-Air Temperature
OAVP Outdoor-Air Velocity Pressure
PRES Pressurization
PURG Purge
RAT Return-Air Temperature
RFVC Return Fan Volume Control
RH Relative Humidity
RVP Return Velocity Pressure
SAT Supply-Air Temperature
SF Supply Fan Relay
SP Static Pressure
SPT Space Temperature
SVP Supply Velocity Pressure
TEMP Optional Temperature Input
*Available on VAV only.
†Discrete output with two-position damper control.