York 00497VIP Thermostat User Manual


 
YORK INTERNATIONAL62
DipSW 2-1= on Printing Columns - 40
2-2 = on User Font Back-up - on
2-3 = on Character Select - normal
2-4 = off Zero - slash
2-5 = on International character set -
American
2-6 = on International character set -
American
2-7 = on International character set -
American
2-8 = off International character set -
American
DipSW 3-1= on Data length - 8 bits
3-2 = on Parity Setting - no
3-3 = on Parity condition - odd
3-4 = on Busy control - H/W busy
3-5 = on Baud rate select - 1200*
3-6 = off Baud rate select - 1200*
3-7 = on Baud rate select - 1200*
3-8 = off Baud rate select - 1200*
* Settings shown for 1200 Baud. Other Baud rates can
be selected. Refer to Printer manufacturer’s manual
supplied with Printer.
OPTIVIEW REMOTE
CONTROL CENTER SETUP
Number of Units Connected
Using the Setpoints Screen, enter the number of chiller
units to communicate with. The identication number
of the chiller unit which is setup at the unit’s control
panel can not exceed this number. The identication
number will appear at the top of each report.
Printer Setup
Using the PRINTER Screen, the OptiView Remote
Control Center must be congured to transmit data in
the same format as the Printer is congured to receive
the data. The following values must be entered.
Baud Rate - Set as desired. Value selected must be
the same as Printer conguration above.
Data Bits - 8
Parity - None
Stop Bits - 1
Printer Type
Using the PRINTER Screen, the actual Printer type
connected to the OptiView Remote Control Center
must be entered. Selection determines the control codes
that are sent to the Printer. These codes determine
such things as lines per inch, character width and
general formatting. Available selections are: Okidata,
Weigh-Tronix and Seiko.
Automatic Data Logging
If automatic data logging is desired, a Status Report
can be automatically printed at a specied interval
beginning at a specified time, using the PRINTER
Screen. The interval is programmable over the range of
1 minute to 1440 minutes in 1 minute increments. The
rst print will occur at the programmed START time
and occur at the programmed OUTPUT INTERVAL
thereafter. The time remaining until the next print is
displayed on the PRINTER Screen.
Automatic Printer Logging - Enables and disables
automatic data logging
Log Start Time - Enter the time the rst print is
desired.
Log Unit Selected - Select a unit or all units to
print logs of.
Output Interval - Enter the desired interval between
prints.
Print
Pressing the Print button from the Unit Screen allows
the operator to obtain a printout of current system
operating parameters for the currently selected unit.
A sample operating data printout for a YCAS chiller
is shown following.
Printers