DMP Electronics XR500 Home Security System User Manual


 
XR500 Series Canadian Programming Guide Digital Monitoring Products
65
aPPendiX
23.4 Using the Walk Test
The XR500 Series Canadian panel provides a walk test feature that allows a single technician to test the
protectiondevicesconnectedtozonesonthesystem.ConducttheWalkTestwithin30minutesofresetting
thepanel.TheWalkTestautomaticallyendsifnozonesaretrippedfor20minutes.TESTINPROGRESS
displaysatallkeypadsprogrammedwiththesameAreaDisplayfeatures.Whenveminutesremain,TEST
ENDWARNINGdisplays.TheWalkTestonlytestszonesassignedtotheareasprogrammedintothekeypad
inAreaDisplay.IfanyareasarearmedtheWalkTestdoesnotstartandSYSTEMARMEDdisplays.
WALK TEST
Walk Test
ToconducttheWalkTest,resetthecontrolpanelbymomentarilyplacingajumper
onJ16.Fromthekeypad,enterthecode8144.ThekeypaddisplaysWALKTEST
for four seconds. If the system is monitored and the communication type is DD or
NET, the system sends a System Test Begin report to the central station. After four
seconds, the keypad displays the zone type choices for testing.
Note: If ENHANCED ZONE TESTinSystemOptionsissettoYES,theWalkTestcan
be limited to only operate during the Area 32, Shift 4 schedule if programmed. If no
schedule is entered, the walk test always operates.
BG FI PN SV
Zone Types
Select the zone type you want to test. An asterisk next to the zone type indicates
the zone type chosen for testing. Press the Select key again to deselect the zone
type.Whenyouhaveselectedallthezonetypesyouwantfortesting,pressthe
COMMANDkeytodisplaythenextWalkTestoption.PressingtheBackArrowkey
exitstheWalkTest.
Note:FortheWirelessCheck-inTest,makesurenozonetypesareselectedand
presstheCOMMANDkey.PressingtheBackArrowkeyexitstheWalkTest.
BG(Burglaryzones)-SelectBG to test burglary zones. Includes all NT, DY, EX, A1,
and A2 zones.
FI(Firezones)-SelectFItotestrezones.IncludesallFIandFVzones.
PN(Paniczones)-SelectPN to test panic zones. Includes all PN and EM zones.
SV(Supervisoryzones)-SelectSV to test supervisory zones. Includes all SV zones.
Note: DuringtheWalkTest,tripeachzonedeviceorbuttononthesystemfor1to2
seconds. You do NOT have to hold the zones for 2 seconds in normal mode for PN
typezones.YouareonlyrequiredtoholdthepanicduringtheWalkTestbecause
the zone takes additional time to report when the system is in test mode.
WLS PIR
WLS(WirelessCheck-inTest)-SelectWLStoautomaticallytestwirelesstransmitter
communications. Includes all wireless devices except key fobs and transmitters
programmedforasupervisiontimeof0(zero).
PIR(WirelessPIRWalkTest)-ThePIRWalkTestallowstheinstallertoverifythe1126
operation.Whenenabled,the1126LEDasheseachtimemotionisdetectedforupto
30 minutes. This is a local test only and no messages are sent to the Central Station.
BELL NO YES PULS
Bell Action
This option selects the bell output action when a zone under test faults. This option
allowsthepanelbell,and/orburglarybell,and/orrebelltoturnONandthenOFF
eachtimeazoneistripped(openedorshorted).
NO -SelectNOfornobelloutputactionduringWalkTest.
YES - SelectYEStoturnonanybelloutputfor2secondsduringWalkTest.
PULS -SelectPULStoturnonanybelloutputfor1/4secondduringWalkTest.Any
LX-Busdeviceoutputturnsonfor1.6secondsduetothepollingcycle.
TRIPS: XXX END
Trip Counter For Walk Test
OnceintheWalkTest,walkaroundandtripeachprotectivedevice.Continue
tripping devices until the entire system is tested.
WitheachzonetripduringtheWalkTest:
• Keypaddisplayincrementseachtimeaselectedzoneisopenedorshorted
• Thekeypadbuzzesfortwoseconds
• ThepanelsoundsthealarmbellsasprogrammedinBellAction
• EachtimeaFI,FV,orSVzonetrips,aSensorResetoccurs.