DMP Electronics XR500 Home Security System User Manual


 
XR500 Series Canadian Programming Guide Digital Monitoring Products
59
zone informaTion
19.25
PRIORITY NO YES
Priority
Select YES to provide additional protection for the premises by requiring this zone to
be in a normal condition before its assigned area can be armed.
19.26 Fire Panel Slave Input
ThisoptionisavailableonFireZones(FI)onlyandallowsarezonetheabilityto
provideslavecommunicationoperationforaseparaterealarmcontrolpanel.If
YES,thiszonewilltransmitarestoralimmediatelywhenrestoredbytherepanel
being monitored. A sensor reset is not required to generate the restoral message.
IfNO,thiszonewilloperateasastandardretypezoneandasensorresetis
requiredbeforethezonewillreturntonormal.DefaultisNO.
19.27 Area Follower
Allows Night, Day, Aux 1, or Aux 2 burglary zones to be delayed by following any exit
orentrydelaythatiscurrentlyrunningintheareathatisspecied.Defaultis0.
19.28 Zone Real-Time Status
SelectingYESallowsReal-TimeStatusreports,suchasDoorOpenorClosedwith
zonenumber,tobesentusingPCLogreporting.SelectingNOdisablesReal-Time
Statusforthiszone.DefaultisNO.
19.28.1 Door Number
IfZONEREAL-TIMESTATUSisselectedasYES,enteradoornumber(keypadbus
address)of1-16.Whenadoornumberisselected,thedoornumberisincluded
inthestatusreportinsteadofthezonenumber.Enter0(zero)todisablethis
featureandreportthezonenumber.Defaultis0(nodoor).
19.29
ZONE AUDIT DAYS:
Zone Audit Days
Enterthenumberofdays(0to365)allowedtoelapsewithoutthezonebeingtripped
beforeafaultmessageissent.Themessageissenttothereceiver(s)programmed
toreceiveSupervisory/TroubleReportsat10:00amfollowingtheexpirationofthe
timer.Eachtimethezoneistripped,theZoneAuditDaystimerrestartsandbegins
to countdown the number of days programmed. After the countdown expires, a fault
messageissentandtheZoneAuditDaystimerrestartsandbeginstocountdownthe
numberofdaysprogrammed.Availableforallzonetypesexceptreandreverify.
Enter0(zero)todisablethisfunction.Defaultis0(zero).
19.30 Report with Account Number for Area
Thisoptionisonlyavailablefor24-hourzonetypes(Fire,FireVerify,Panic,
Emergency,orSupervisory).
Entertheareanumber(1-32)toassignasa24-hourzonetype.Thisoption
sends
the account number of the programmed area with messages. If the entered area
number does not exist or is not valid, the account number programmed in the
Communicationsectionissent.Select0(zero)tohavethereportsentwiththe
account number programmed in Communication. Default is 0
FOLLOW AREA: 0
ZONE REAL-TIME
STATUS
NO YES
FIRE PANEL SLAVE
INPUT: NO YES
DOOR NUMBER: 0
0
REPORT WITH ACCT
NO. FOR AREA: 0