Mitsumi electronic G-50A Air Conditioner User Manual


 
86
Table 13-5 Recommended IP address setting range
Models
G-50A main body
PC for monitoring
PC for centralized control (TG-2000A)
PLC
PC for initial setting tool
IP address setting range
[192.168.1.001] ~ [192.168.1.040]
[192.168.1.101] ~ [192.168.1.149]
[192.168.1.150]
[192.168.1.151] ~ [192.168.1.200]
[192.168.1.151] ~ [192.168.1.155] for pulse count
[192.168.1.171] ~ [192.168.1.190] for general-purpose controller
[192.168.1.201]
13.2.1 Setting method for connecting G-50A to exclusive LAN
This is a setting method to establish G-50A system with exclusive LAN wiring
(1) Setting of IP address
In the case that LAN wiring is newly provided for G-50A system, allocate the IP address of G-50A from
[192.168.1.1] in sequence. For example, assign [192.168.1.1] for the first G-50A, [192.168.1.2] for the
second G-50A, and so and so in sequence. In addition, set a PC for monitoring on the Web to monitor
G-50A and set the initial setting tool and the like also to the network address in the same system.
In case of G-50A exclusive LAN, it is recommended that the IP address of each component is set within
the following IP address range.
As the default value of IP address for G-50A is [192.168.1.1], the address from the second G-50A must
be changed.
(2) Setting of subnet mask
Set [255.255.255.0] (default value) typically.
* Some models among hubs are provided with exclusive port for connecting between hubs.
For G-50A and PC for monitoring, connect to the regular port.
10BASE-T LAN straight cable
HUB
1st G-50A 2nd G-50A
Integrated software: TG2000A Initial setting tool
IP address: 192.168.1.1
Sub-net mask: 255.255.255.0
IP address: 192.168.1.1
Sub-net mask: 255.255.255.0
IP address: 192.168.1.101
Sub-net mask: 255.255.255.0
IP address: 192.168.1.201
Sub-net mask: 255.255.255.0
Figure 13-1 Setting example for exclusive LAN system