Mitsumi electronic G-50A Air Conditioner User Manual


 
53
The standing charge is only added at calculation on the clearance day, and printed
out after summing up the air conditioning charge. Printing out is not available for the
calculation of specified day.
CAUTION
(3) Apportioning by apportioning standard data
To calculate [Power consumption per indoor unit], multiply the operation time by the standard data being
calculated for each indoor unit per charging time frame with each capacity. Sum up this [Power
consumption per indoor unit] for the indoor units inside the watt-hour meter to obtain [Indoor unit total
power consumption]. Using a ratio of these two data, calculate [Daily power consumption by indoor unit]
once a day.
(4) Processing on clearance day
On the clearance day, sum up [Daily power consumption by indoor unit] for each tenant (charge block)
and add the standing charge to calculate the monthly electric charge.
Integrated operation
time of charging
time frame 1
Total power consumption of indoor units
Power consumption of indoor unit 1
4.5kW
Power consumption
of indoor unit 1
Power consumption
of indoor unit 2
Charging time frame 1
Charging time frame 1
Charging time frame 1
Daily power
consumption
Example) 97.84kW
Daily power
consumption
of indoor unit 1
For crankcase heater
Example) 2.16kW