A SERVICE OF

logo

19
[Example to use relay board]
(2) In case of K-control Y-series system
Total wiring length (p): 500m or less, when exceeded this length, be sure to use the relay board.
Figure 4-4 Relay board wiring example
Centralized control
system M-NET bus
K-control Mr.Slim
air conditioner
indoor unit
K-transmission
converter
Relay board Relay board
Local
remote
controller
K-control Mr.Slim
air conditioner
indoor unit
Local
remote
controller
K-control Mr.Slim
air conditioner
indoor unit
Local
remote
controller
K-control Mr.Slim
air conditioner
indoor unit
Local
remote
controller
m
m
m
Figure 4-5 K-control Y-series wiring example
Centralized control
system M-NET bus
K-control
Y-series
indoor unit
K-transmission
converter
K-control
Y-series
outdoor unit
K-control
Y-series
outdoor unit
Local
remote
controller
K-control
Y-series
indoor unit
Local
remote
controller
K-control
Y-series
indoor unit
Local
remote
controller
p
(3) In case of system where K-control Mr.Slim air conditioner and Y-series are mixed
Be sure to use the relay board as shown in the figure below, and connect the indoor unit of K-control
Mr.Slim air conditioner to the secondary side of the relay board.
Figure 4-6 K-control mixing system example
Centralized control
system M-NET bus
K-control Mr.Slim
air conditioner
indoor unit
K-control
Y-series
outdoor unit
K-transmission
converter
Relay board
Local
remote
controller
K-control Mr.Slim
air conditioner
indoor unit
Local
remote
controller
K-control
Y-series
indoor unit
Local
remote
controller
p
[Caution for wiring connection work]
The wiring connection work of the equipment delivered (MELANS equipment, air
conditioning equipment, etc.) including power and earth lines.
Install the transmission line and signal line apart from the power line and earth
line. If not, the noise from the power/earth lines will mix into the transmission line
or signal line causing to generate erroneous operation.
In case of shielded line, provide one-point grounding at each transmission line.
(Relay shielded line at the terminal block of each equipment.)
CAUTION