Mitsumi electronic G-50A Air Conditioner User Manual


 
22
5.1.3 Selecting the power supply unit
G-50A is driven by DC12V from the Power supply unit : PAC-SC50KUA. To communicate with the air
conditioner, it is necessary to connect to the M-NET transmission line in addition.
First determine whether G-50A is connected to the centralized control transmission line or to the
indoor/outdoor transmission line.
Figure 5-4 Caution for power supply
Figure 5-5 Connection of centralized control transmission line
To connect with the indoor/outdoor transmission line,
connect the DC12V output (TB3) of PAC-SC50KUA to
G-50A only. For the M-NET terminal (TB2) of G-50A,
connect the indoor/outdoor transmission line.
Never connect M-NET line to the M-NET terminal (TB2) of
PAC-SC50KUA.
Allow the wiring length of DC12V up to 10m maximum.
Please observe the following restrictions also.
- Connect the power supply connector to CN40 on the one
- outdoor unit only.
- To use the power consumption apportioning function,
- do not install on the indoor/outdoor transmission line.
To connect with the centralized
control transmission line,
leave the power supply
connector of the outdoor unit
being connected to CN41.
Centralized control
transmission line
Indoor/outdoor transmission line
TB3
(DC12V)
TB2
(M-NET)
G-50A
Outdoor unit
Power supply unit
PAC-SC50KUA
ME remote controller
TB3
(DC12V)
TB2
(M-NET)
Power supply unit
PAC-SC50KUA
G-50A
Connectable wit Lossnay remote controller
but with restriction on the connecting numbers
TB3
(DC12V)
TB2
(M-NET)
Upper class SC
Lower class SC
Transmission line
booster unit
(PAC-SF46EP)
No. 000 unit
No.201 unit
Lossnay Lossnay Lossnay
Power supply unit
PAC-SC50KUA
Centralized control
transmission line
Indoor/outdoor transmission line
Indoor/outdoor transmission line
As G-50A works to back up each data, recommend to install it on the centralized
control transmission line.
If G-50A is installed on the indoor/outdoor transmission line, communication can
not be performed even with air conditioners in other systems at power failure if
occurred on the connected outdoor unit. To use the power consumption
apportioning function, therefore, be sure to install it on the centralized control
transmission line.
CAUTION
(1) Connecting to the centralized control transmission line
The Power supply unit : PAC-SC50KUA is required.