5. Explanation of Devices
5.3 Detailed Explanation of Devices
- 68 -
100ms Integrated timer T
(a) When the input conditions are set, the count starts. When the set value is counted, that timer contact
will turn ON.
(b) Even the input conditions are turned OFF, the 100ms integrated timer current value (count value)
will be held, and the contact state will not change.
(c) The 100ms integrated timer count value will be set to 0 and the contact will turn OFF when the RST
command is executed.
T101 K100
X5
100ms integrated timer
Input conditions
T101 coll OFF
T101 contact OFF
X5 OFF
ON
ON
9 seconds
RST T101
X7
T101 reset command
X7 OFF
ON
9 seconds
6 seconds
6 seconds
ON
1.5 seconds
1 seconds
T233 current value
Reset input
~
0 1 90 91 100 0 1 60
~
~
(d) The value is set with a decimal, and can be designated from 1 to 32767 (0.1 to 3267.7 s). The data
register (D) data can also be used as the setting value. File register (R) cannot be used.
(e) When the bit selection parameter is set, the 100ms integrated timer current value (count value) will
be held even when the power is turned OFF.
(2) Setting of timer setting value from setting and display unit
The timer setting value can be set with the setting and display unit using device T0 to T103.
(Variable timer)
Whether the setting value (Kn) programmed with the sequence program or the setting value set
from the setting and display unit is valid is selected with the bit selection parameters. The
changeover is made in a group for T0 to T103. Even when set from the setting and display unit,
the setting value (Kn) program will be required in the sequence program. However, the Kn value
will be ignored. When the data register (D) is used for the setting value, the data register (D)
details will be used as the setting value regardless of the parameter.