7. Basic Commands
OUT (C)
- 124 -
{ OUT (C) ... Counter output
Usable device
Digit
desig-
nation
Index
No. of
steps
Bit device Word device
Con-
stant
Pointer
X Y M L F B SB T SM V T C D R W SW Z SD K H P
Device
{
Setting
value
{
{ {
{
3
C1 D10
C0 K50
Device No.(C0 to 127)
Setting value
(1 to 32767 is valid)
Setting value
(1 to 32767 is valid for
the data register details)
Device No.(C0 to 127)
Function
(1) If the operation results before the OUT command change from OFF to ON, the current value
(count value) will be incremented by one. When the value is counted up (current value >= setting
value), the contacts will change as shown below.
A contact Continuity
B contact Non-continuity
(2) The value will not be counted when the operation results are ON. (A pulse change is not required
to input the count.)
(3) If the operation results change from OFF to ON after the current value >= setting value is
established, the contact state will remain the same and the current value will not be counted up.
Execution condition
This is executed per scan regardless of the operation results before the OUT command.