[ II Restrictions ]
- 61 -
HWE09080 GB
(5) Size of the refrigerant pipe between the first distributor or the second distributor and heat source units
Heat source unit
model
Composing unit models Liquid pipe (mm) [inch] Gas pipe (mm) [inch]
P144 P72 ø9.52 [3/8"] ø19.05 [3/4"]
P72
P168 P96 ø9.52 [3/8"] ø22.2 [7/8"]
P72
P192 P96
P96
P216 P120 ø12.7 [1/2"] ø22.2 [7/8"]
P96
P240 P120
P120
P264 P96 ø12.7 [1/2"] ø22.2 [7/8"]
P96
P72
P288 P96
P96
P96
P312 P120
P96
P96
P336 P120
P120
P96
P360 P120
P120
P120