Mitsubishi Electronics r410a Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 289 -
HWE09080 GB
1. Error Code
Function setting error
2. Error source, cause, check method and remedy
1. Error Code
Model setting error
2. Error source, cause, check method and remedy
1. Error Code
Incompatible unit combination
2. Error definition and error detection method
The check code will appear when the indoor units with different refrigerant systems are connected.
3. Error source, cause, check method and remedy
7113
Error source Cause Check method and remedy
Heat source
unit
(1) Wiring failure 1) Control board connector
Check the CNTYP2,4,5 connector connection.
Inverter board connector
Check the CNTYP connector connection.
(2) Disconnected connector, short cir-
cuit, contact failure
2) Check the compatibility of the circuit board, and replace
it with a correct one if necessary.
(3) Incompatibility between the control
board and inverter board (Replace-
ment of the circuit board with the
wrong one)
3) Check the model selection switch on the heat source
unit (Dipswitch SW5-7 on the control board.).
7117
Error source Cause Check method and remedy
Heat source
unit
(1) Wiring failure 1) Control board connector
Check the CNTYP2,4,5 connector connec-
tion.
Inverter board connection
Check the CNTYP connector connection
(2) Disconnected connector, short circuit, contact
failure
7130
Error source Cause Check method and remedy
Heat source
unit
The connected indoor unit or BC controller is
exclusively for use with R22 or R407C. An in-
compatible indoor unit or BC controller is con-
nected.
The M-NET connection adapter is connected
to the indoor unit system in a system in which
the Slim Model (A control) of units are con-
nected to the M-NET.
Check the model names of the connected in-
door unit and the BC controller.
Check whether the connecting adapter for
M-NET is not connected to the indoor unit.
(Connect the connecting adapter for M-NET
to the heat source unit.)