[ VII Control ]
- 144 -
HWE09080 GB
-5- Bypass Control
Bypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the following functions.
(1) Bypass solenoid valve (SV1a) (ON = Open)
(2) Bypass solenoid valve (SV9) (ON = Close)
Operation
SV1a
ON OFF
When the compressor on each heat source
unit starts up
ON for 4 minutes.
After the restoration of thermo or 3 minutes
after restart
ON for 4 minutes.
During cooling or heating operation with the
compressor stopped
Always ON.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
After the operation has stopped ON for 3 minutes.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
During defrost operation ON
While the compressor is operating at the
minimum frequency and when the low pres-
sure (63LS) drops (3 or more minutes after
compressor startup)
When low pressure (63LS) drops
below 0.23MPa[33psi].
When low pressure (63LS) ex-
ceeds 0.38MPa[55psi].
When high pressure (63HS1) rises When 63HS1 exceeds
3.62MPa[525psi]
When 63HS1 is or below
3.43MPa[497psi] and 30 seconds
have passed
Operation
SV9
OFF ON
When high pressure (63HS1) rises during
the heating operation
When 63HS1 exceeds 3.50MPa
[507psi]
When the pressure is
2.70MPa[391psi]or below
Others Always ON