(1) Indoor unit operation mode
The operation mode can be selected from the following 6 modes using the remote controller.
(2) Heat source unit operation mode
When units in cooing and heating coexist, the operation mode (cooling main mode or heating main mode) will be determined
by the heat source unit, based on the refrigerant pressure and speed variation data.
(3) Operation pattern for automatic cooling/heating mode
When the automatic cooling/heating mode is selected from remote controller functions, the indoor temperature will be detect-
ed in pattern as shown in the figure below, and the operation mode (cooling or heating) will automatically be selected.
(4) Relationship between the operation mode and the load capacity (kW) (within a system)
1 Cooling mode
2 Heating mode
3 Dry mode
4 Automatic cooling/heating
mode
5Fan mode
6 Stopping mode
1 Cooling only mode All indoor units in operation are in cooling mode.
2 Heating only mode All indoor units in operation are in heating mode.
3 Cooling main mode Coexistence of units in cooling and heating modes.
4 Heating main mode Coexistence of units in cooling and heating modes.
5 Stopping mode All indoor units are in fan mode or stopping mode.
Cooling
Fan
Heating
Switches to cooling mode
Cooling operation under
Thermo-ON conditions
Set temperature
(Variable between 19 C and 28 C
[ 67 F and 83 F])
Heating operation under Thermo-ON conditions
Switches to heating mode
Fan
Temperature
rise
1.5 C
[3 F]
1.5 C
[3 F]
1 C [2 F]
1 C [2 F]
Cooling load
capacity
Heating load
capacity
+
Cooling load
capacity
Heating load
capacity
Heating load
capacity
+
Cooling load
capacity
100(%)
Cooling only
mode
Cooling main
mode
Heating main
mode
Total heat recovery mode
Heating only
mode
100(%)
Heating
load (%)
Heating load
X100 = Cooling
load (%)
=
Cooling load
X 100
0