[1] System configuration
1. Table of compatible indoor units <PQHY>
The table below summarizes the types of indoor units that are compatible with different types of heat source units.
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given heat source unit exceeds the capacity of the heat source
unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a com-
bination of units so that the total capacity of the connected indoor units is at or below the capacity of the heat source unit
whenever possible.
1. Table of compatible indoor units <PQRY>
The table below summarizes the types of indoor units that are compatible with different types of heat source units.
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given heat source unit exceeds the capacity of the heat source
unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a com-
bination of units so that the total capacity of the connected indoor units is at or below the capacity of the heat source unit
whenever possible.
Heat
source
units
Composing units Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
P72 - - - 36 - 93 1 - 15 P06 - P96 models
R410A series indoor units
P96 - - - 48 - 124 1 - 20
P120 - - - 60 - 156 1 - 26
P144 P72 P72 - 72 - 187 1 - 31
P168 P96 P72 - 84 - 218 1 - 36
P192 P96 P96 - 96 - 249 1 - 41
P216 P120 P96 - 108 - 280 2 - 46
P240 P120 P120 - 120 - 312
2 - 50
P264 P96 P96 P72 132 - 343
P288 P96 P96 P96 144 - 374
P312 P120 P96 P96 156- 405
P336 P120 P120 P96 168 - 436
P360 P120 P120 P120 180 - 468
Heat
source
units
Composing units Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
P72 - - 36- 108 1 - 18 P06 - P96 models
R410A series indoor units
P96 - - 48 - 144 1 - 24
P120 - - 60 - 180 1 - 30
P144 P72 P72 72 - 216 1 - 36
P168 P96 P72 84 - 252 1 - 42
P192 P96 P96 96 - 288 1 - 48
P216 P120 P96 108 - 324
2 - 50
P240 P120 P120 120 - 360