Mitsubishi Electronics r410a Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 214 -
HWE09080 GB
Item
Heat source unit model
PQRY-P120YHMU-A
Model name of BC controller CMB-P104NU-G
Operating
conditions
Indoor temperature DB/WB
21.1°C/í
[70 °F/í]
Heat source water temperature °C [ °F] 21.1[70]
Heat source water flow rate
m
3
/h
[G/h]
[gpm]
5.76
[1522]
[25.4]
Indoor
unit
No. of connected units
Unit
3
No. of units in operation 3
Model í 36/36/48
Pipe
length
Main pipe
m [ft]
5 [16-3/8]
Branch pipe 10 [32-3/4]
Total pipe length 35 [115]
Fan speed í Hi
Refrigerant charge
kg
[lbs-oz]
13.6 [30]
Heat source
unit
Current A 28.3
Voltage V 230
Compressor frequency Hz 90
LEV opening
Indoor unit
Pulse
332/332/406
BC controller (1/2/3) 110/í/660
Pressure
switch
High pressure (63HS1)/
Low pressure (63LS)
MPa
[psi]
2.68/0.80
[389/116]
BC controller on the liquid side
(PS1)/Intermediate part (PS3)
2.64/2.32
[383/336]
Sectional
temperatures
Heat
source
unit
Discharge (TH4)
°C [ °F]
81 [178]
Heat exchanger outlet 5 [41]
Accumulator inlet 4 [39]
Accumulator outlet 4 [39]
Compressor inlet 4 [39]
Compressor shell bottom 40 [104]
Indoor
unit
LEV inlet 39 [102]
Heat exchanger inlet 70 [158]