Mitsubishi Electronics r410a Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 266 -
HWE09080 GB
1. Error Code
Address overlaps
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
1. Error Code
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
3. Cause, check method and remedy
6600
Cause Check method and remedy
Two or more of the following have the same address:
Heat source units, indoor units, LOSSNAY units, con-
trollers such as M-NET remote controllers.
<Example>
6600 "01" appears on the remote controller
Unit #01 detected the error.
Two or more units in the system have 01 as their ad-
dress.
Find the unit that has the same address as that of the
error source.
Once the unit is found, correct the address. Then,
turn off the heat source units, indoor units, and
LOSSNAY units, keep them all turned off for at least
five minutes, and turn them back on.
6601
Cause Check method and remedy
(1) No voltage is applied to the M-NET transmission
line.
Check if power is supplied to the M-NET transmission
line and correct any problem found.
(2) M-NET transmission line is short-circuited.