Mitsubishi Electronics FX3UC Garage Door Opener User Manual


 
933
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-4 Applied Instruction Execution Time
31
FNC277-FNC279
Data
Transfer 3
32
FNC280-FNC289
High-Speed
Processing 2
33
FNC290-FNC299
Extension File
Register Control
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
•FX3U/FX3UC PLCs
FNC
No.
Instruction
Execution time in ON status (µs) Execution time in OFF status (µs)
Remarks
16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction
Program flow
00 CJ 8.0 0.195
01 CALL
13.5
(CALL+SRET)
0.195
02 SRET ⎯⎯⎯
03 IRET 4.4 ⎯⎯⎯
04 EI 3.8 ⎯⎯⎯
05 DI 3.7 ⎯⎯⎯
06 FEND
113.9 + 2.13X +
3.25Y
⎯⎯⎯
Even if FEND and END are used
together, execution time of only
END is required.
X: Number of input points,
Y: Number of output points
07 WDT 5.4 0.065
08 FOR
11.6
(FOR + NEXT)
⎯⎯⎯
09 NEXT ⎯⎯⎯
Move and compare
10 CMP 15.5 16.0 0.455 0.845
11 ZCP 18.9 19.7 0.585 1.105
12 MOV 0.64 1.48 0.32 1.48
For details, refer to
Appendix B-6-2.
13 SMOV 22.9 0.715
14 CML 10.6 10.2 0.325 0.585
15 BMOV 13.9 + 0.44n 0.455
16 FMOV 14.2 + 0.19n 14.0 + 0.38n 0.455 0.845
17 XCH 10.7 11.4 0.325 0.585
18 BCD 7.94 12.49 0.325 0.585
19 BIN 4.38 5.32 0.325 0.585
Arithmetic and logical operation
20 ADD 4.77 5.72 0.455 0.845
21 SUB 4.82 5.78 0.455 0.845
22 MUL 4.6 5.7 0.455 0.845
23 DIV 6.3 7.67 0.455 0.845
24 INC 6.2 6.4 0.195 0.325
25 DEC 6.2 6.4 0.195 0.325
26 WAND 3.57 4.55 0.455 0.845
27 WOR 3.57 4.55 0.455 0.845
28 WXOR 3.57 4.55 0.455 0.845
29 NEG 7.6 8.0 0.195 0.325
Rotation and shift
30 ROR 10.5 11.5 0.325 0.585
31 ROL 10.5 11.5 0.325 0.585
32 RCR 10.9 11.8 0.325 0.585
33 RCL 10.9 11.8 0.325 0.585
34 SFTR 23.2 + 0.08n 0.585
35 SFTL 23.2 + 0.08n 0.585
36 WSFR 7.5 + 0.44n 0.585
37 WSFL 7.5 + 0.44n 0.585
38 SFWR 8.1 0.455
39 SFRD 7.7 0.455