FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
A Programming Tool Applicability and Version Upgrade History
A-1 Programming Tool Applicability
31
FNC277-FNC279
Data
Transfer 3
32
FNC280-FNC289
High-Speed
Processing 2
33
FNC290-FNC299
Extension File
Register Control
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
2. In the case of programming tool (version)
Even using a programming tool not applicable to the FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs, programming is enabled
when an alternative model is set.
Using an alternative model
*1. For Ver. 8.18U to 8.24A of GX Developer, the PLC type is FX3UC.
*2. "FX
2N" is selected when the FX-10P(-E) is used.
Contents of restrictions
Programming is enabled only in the function ranges such as instruction/device range and program size
available in both the PLC model to be programmed and the alternative PLC model.
In the FX
3S PLC, memory capacity setting of the PLC parameter must be set to 4,000 steps or less.
Use a programming tool which can select FX
3S, FX3G, FX3GC, FX3U or FX3UC when changing the
parameters such as memory capacity and file register capacity.
Use a programming tool which can select FX
3G when executing communication using the standard (USB)
built-in port of the FX
3S/FX3G/FX3GC PLCs.
3. Program transfer speed and programming tools
In FX3S/FX3G/FX3GC PLCs
1) Built-in USB communication
The FX
3S/FX3G/FX3GC PLCs has a built-in USB communication port, and performs program writing, program
reading and monitoring at high speed (12 Mbps) with a personal computer that supports USB.
a) Supported programming tools
*3
GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later)
b) In programming tools not supporting USB
Communication is performed via RS-422 or RS-232C.
2) RS-422/RS-232C communication
The FX
3S/FX3G/FX3GC PLCs can write and read programs and perform monitoring at 115.2 kbps through RS-422/
RS-232C communication.
a) 115.2 kbps supported programming tools
*3
GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later), FX-30P (Ver. 1.00 or later)
b) 115.2 kbps supported interfaces
- Standard built-in port(RS-422) or expansion board FX
3G-422-BD for RS-422
When the RS-232C/RS-422 converter FX-232AWC-H is connected.
- Expansion board FX
3G-232-BD for RS-232C
- Special adapter FX
3U-232ADP(-MB) for RS-232C
c) In programming tools not supporting 115.2 kbps
Communication is executed at 9,600 or 19,200 bps.
*3. Select "FX3G" for a programming tool not supporting FX
3S/FX3GC PLCs.
Model to be programmed Model to be set Priority High Low
FX3S PLC FX3S FX3G
FX1N
*2
FX2N
*2
FX3G PLC FX3G
FX1N
*4
FX2N
*2
FX2
FX3GC PLC FX3GC FX3G
FX1N
*2
FX2N
*2
FX3U PLC
FX3U(C)
*1
FX3UC FX2N FX2
FX3UC PLC
FX3U(C)
*1
FX3UC FX2N FX2