Mitsubishi Electronics FX3UC Garage Door Opener User Manual


 
593
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
24 Others – FNC181 to FNC189
24.4 FNC188 – CRC / Cyclic Redundancy Check
21
FNC160-FNC169
Real Time Clock
Control
22
FNC170-FNC179
External Device
23
FNC180
Alternate
Instructions
24
FNC181-FNC189
Others
25
FNC190-FNC199
Block Data
Operation
26
FNC200-FNC209
Character String
Control
27
FNC210-FNC219
Data
Operation 3
28
FNC220-FNC249
Data
Comparison
29
FNC250-FNC269
Data Table
Operation
30
FNC270-FNC276
Ex-Device
16-bit conversion mode (while M8161 is OFF)
In this mode, the operation is executed for high-order 8 bits (1 byte) and low-order 8 bits (1 byte) of a device specified
in .
The operation result is stored to one 16-bit device specified in .
8-bit conversion mode (while M8161 is ON)
In this mode, the operation is executed only for low-order 8 bits (low-order 1 byte) of a device specified by .
With regard to the operation result, low-order 8 bits (1 byte) are stored to a device specified by , and high-order
8 bits (1 byte) are stored to a device specified by +1.
Example: = D100
=D0
n = 6
Device
Contents of target data
8 bits 16 bits
Device storing data for which
the CRC value is generated
Low-order byte Low-order bits of D100 01H
0301H
High-order byte High-order bits of D100 03H
+1
Low-order byte Low-order bits of D101 03H
0203H
High-order byte High-order bits of D101 02H
+2
Low-order byte Low-order bits of D102 00H
1400H
High-order byte High-order bits of D102 14H
...
...
+n/2-1
Low-order byte
High-order byte
Device storing the generated
CRC value
Low-order byte Low-order bits of D0 E4H
41E4H
High-order byte High-order bits of D0 41H
Example: = D100
=D0
n = 6
Device Contents of target data
Device storing data for
which the CRC value is
generated
Low-order byte Low-order bits of D100 01H
+1
Low-order byte Low-order bits of D101 03H
+2
Low-order byte Low-order bits of D102 03H
+3
Low-order byte Low-order bits of D103 02H
+4
Low-order byte Low-order bits of D104 00H
+5
Low-order byte Low-order bits of D105 14H
...
+n-1
Low-order byte
Device storing the
generated CRC value
Low-order byte Low-order bits of D0 E4H
+1
Low-order byte Low-order bits of D1 41H
S
D
16-bit conversion mode
FNC188
CRC
n
M8161
M8000
Command
input
D
S
S
D
S
S
S
S
D
S
D
D
FNC188
CRC
n
M8161
M8000
8-bit conversion mode
Command
input
D
S
S
D
S
S
S
S
S
S
S
D
D