2 Overview (Sequence Program)
2.3 Analog/Positioning Special Control
1
Introduction
2
Overview
3
Instruction
List
4
Devices
in Detail
5
Specified the
Device &
Constant
6
Before
Programming
7
Basic
Instruction
8
FNC00-FNC09
Program Flow
9
FNC10-FNC19
Move & Compare
10
FNC20-FNC29
Arith. & Logic
Operation
2.3 Analog/Positioning Special Control
For details, refer to the manual of each product.
1. Analog I/O control
Analog input
Analog output
Pt100 temperature sensor input
Thermocouple temperature sensor input
Block dedicated to temperature control
2. Positioning control
SSCNETΙΙΙ - Positioning Block.
Pulse output block (controlled by sequence
program)
Positioning unit (controlled by instructions
dedicated to positioning)
Cam switch (resolver detection)
3. High-speed counter
High-speed counter (hardware counter equipped
with multiplication function)
2.4 Link and Communication
FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs support the following communication functions:
1. CC-Link
The CC-Link system can be constructed with an
FX
3G/FX3GC/FX3U/FX3UC PLCs working as the
master station.
An A or QnA PLC can work as the master station,
and FX PLCs can be connected as remote device
stations.
A Q PLC can work as the master station, and FX
PLCs can be connected to remote device stations or
intelligent device stations.
The CC-Link is an open network allowing connection
of not only FX PLCs but also inverters, AC servo
systems, and sensors.
Refer to the respective product manual.
2. CC-Link/LT
The CC-Link/LT system can be constructed with an
FX
3G/FX3GC/FX3U/FX3UC PLCs working as the
master station.
General X (input) and Y (output) devices are
assigned to remote I/O units, and operated by
programs for general-purpose I/O.
Refer to the FX
3UC Hardware Edition for the
built-in type CC-Link/LT master.
Refer to the product manual for the
FX
2N-64CL-M.
3. MELSEC I/O LINK
The MELSEC I/O LINK is a remote I/O system
whose
master station is an FX3U/FX3UC (D, DS,
DSS) PLCs.
Units for MELSEC I/O LINK remote I/O system (A
PLCs) can be used as remote units.
Refer to the respective product manual.
4. AS-i system
A network system at the actuator or sensor level can
be constructed with an FX
3U/FX3UC PLCs working as
the master station in the AS-i system.
Refer to the respective product manual.
5. Ethernet communication
An FX PLC can be connected to the host system
such as personal computer or workstation via
Ethernet (100BASE-TX or 10BASE-T) using TCP/IP,
UDP/IP or UDP communication protocol.
Refer to the respective product manual.
6. N : N Network
Up to eight FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs are
connected, and data is automatically transferred
among them.
Refer to the Data Communication Edition.
7. Parallel link
Two PLCs are connected, and data is automatically
transferred between them.
Refer to the Data Communication Edition.
8. Computer link
A computer such as personal computer works as the
master station, up to sixteen FX and A PLCs are
connected to the master station, the master station
directly specifies devices in the PLC, and then data is
transferred.
Protocols in the computer link support the formats 1
and formats 4.
By using MX Component and MX Sheet, monitoring
and logging for the PLC system can be easily set by
Excel
®
.
Refer to the Data Communication Edition.
For MX Component and MX Sheet, refer to the
respective product manual.
9. Non-protocol communication
Non-protocol serial communication is available
between an FX PLCs and interface equipment in
accordance with RS-232C/RS-485 such as bar code
reader, printer, personal computer and measuring
instrument.
Refer to the Data Communication Edition.
10.Inverter communication
An FX PLCs can control up to eight inverters via
communication in accordance with RS-485.
Refer to the Data Communication Edition.
11.MODBUS communication
MODBUS serial communication is available between
an FX PLCs and interface equipment in accordance
with RS-232C/RS-485.
Refer to the MODBUS Serial Communication