Mitsubishi Electronics FX3UC Garage Door Opener User Manual


 
696
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
30 External Device Communication – FNC270 to FNC276
30.6 FNC275 – IVMC / Inverter Multi Command
3. Related devices
For the instruction execution complete flag use method, refer to Subsection 6.5.2.
*1. Cleared when PLC power supply is turned from OFF to ON.
*2. Cleared when the PLC mode switches from STOP to RUN.
*3. Initial value: -1
Cautions
For other cautions, refer to the Data Communication Edition manual.
It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD
(FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same
time.
Number of occupied devices
Two devices are occupied respectively by and .
Make sure not to use those devices in another control.
If a device number outside the range due to indexing, etc. is specified in , the receive data from the inverter
is not stored in . However, values set in and +1 may be written to the inverter.
If any unspecified value is set in , unexpected data may be written to and read from the inverter, and values
of and +1 may be updated.
IVMC instruction reads the inverter status at the time of communication with the inverter, and stores the read status
to . Accordingly, the status written by the IVMC instruction can be read by a next or later read instruction
(IVCK or IVMC).
Applicable inverters
This instruction is applicable to the following inverters:
- FREQROL-E700 (February 2009 and later)
- FREQROL-D700 (Applicable in all)
For details, refer to the respective inverter manual
Applicable programming tool
This instruction is applicable to the following programming tools:
•FX
3S Series PLC
•FX
3G Series PLC
•FX
3GC Series PLC
•FX
3U/FX3UC Series PLCs
Number
Description
Number
Description
ch1 ch2 ch1 ch2
M8029 Instruction execution complete D8063 D8438
Error code of serial communication error
*1
M8063 M8438
Serial communication error
*1
D8150 D8155
Response wait time in inverter communication
*1
M8151 M8156 Inverter communicating D8151 D8156
Step number in inverter communication
*3
M8152 M8157
Inverter communication error
*2
D8152 D8157
Error code of inverter communication error
*2
M8153 M8158
Inverter communication error latch
*2
D8153 D8158
Latch of inverter communication error occurrence step
*2*3
M8154 M8159
Inverter instruction error
*2
D8154 D8159
IVBWR instruction error parameter number
*2*3
Product name Model name Compatible Versions Remarks
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Product name Model name Compatible Versions Remarks
GX Works2 SWDNC-GXW2-E Ver. 1.62Q or later
-
FX-30P Ver. 1.50 or later
Product name Model name Compatible Versions Remarks
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.50 or later
Product name Model name Compatible Versions Remarks
GX Works2 SWDNC-GXW2-E Ver. 1.48A or later
-
FX-30P Ver. 1.20 or later
S
3
D
D
D
S
3
S
3
S
2
D
D
D