Mitsubishi Electronics FX3UC Garage Door Opener User Manual


 
657
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
28 Data Comparison – FNC220 to FNC249
28.2 FNC232~238 – AND=, >, <, < >, <=, >= / Data Comparison
21
FNC160-FNC169
Real Time Clock
Control
22
FNC170-FNC179
External Device
23
FNC180
Alternate
Instructions
24
FNC181-FNC189
Others
25
FNC190-FNC199
Block Data
Operation
26
FNC200-FNC209
Character String
Control
27
FNC210-FNC219
Data
Operation 3
28
FNC220-FNC249
Data
Comparison
29
FNC250-FNC269
Data Table
Operation
30
FNC270-FNC276
Ex-Device
Explanation of function and operation
FNC232 to FNC237 are data comparison instructions connected to other contacts in series.
The contents of are compared with the contents of in binary format, and a contact becomes conductive
(ON) or non-conductive (OFF) depending on the comparison result.
Cautions
1. Negative value
When the most significant bit is "1" in the data stored in or , it is regarded as a negative value in
comparison.
In the 16-bit operation: bit 15
In the 32-bit operation: bit 31
2. When using 32-bit counters (including 32-bit high-speed counters)
Make sure to execute the 32-bit operation (such as "ANDD=", "ANDD>" and "ANDD<") when comparing 32-bit
counters (C200 to C255).
If a 32-bit counter is specified in the 16-bit operation (such as "AND=", "AND>" and "AND<"), a program error or
operation error will occur.
3. Programming of data comparison instructions
When programming in GX Works2 and GX Developer, symbols "" and "" cannot be input.
Separate "" into "<" and "=", and separate "" into ">" and "=".
<Input example for 16-bit operation>
<Input example for 32-bit operation>
Program example
FNC No. 16-bit instruction 32-bit instruction ON condition OFF condition
232 AND= ANDD=
=
233 AND> ANDD>
> <=
234 AND< ANDD<
< >=
236 AND<> ANDD<>
=
237 AND<= ANDD<=
<= <
238 AND>= ANDD>=
>= >
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
S
1
S
2
C10
FNC232
AND=
K200 Y10
D0
FNC236
AND<>
K-10
X000
SET
Y11
D10
FNC233
ANDD>
K678493 M50
M3
X001
X002
S1 S2
When X000 is ON and the current value of the counter
C10 is "200" Y010 is driven.
When X001 is OFF and the contents of the data register
D0 are not "-10", Y011 is set.
When X002 is ON, and the contents of the data registers
D11 and D10 are less than "K678,493", or when M3 turns
ON, M50 is driven.