1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
1
−
43
•
Interface between PULSER connector and differential-output
manual pulse generator/incremental synchronous encoder
Pin No.
PULSER
Connector
Input or
Output
Signal Name
Voltage-Output
Type
Wiring Example Internal Circuit Specification Description
A
+
7
Manual
pulse
generator,
phase A
A
−
17
B
+
8
Manual
pulse
generator,
phase B
B
−
18
P5 6 16
Input
SG 1 5 11 15
•
Rated input
voltage 5.5 VDC
max.
•
HIGH level
3 VDC to 5.25
VDC/2 mA max.
•
LOW level
1 VDC max./ 5 mA
max.
To connect manual
pulse generator
phases A,B
•
Pulse width
5 s min.
10 s min.
(Duty ratio:50%)
5 s min.
•
Rise, fall time
.......1
s max.
•
Phase difference
Phase A
Phase B
2.5 s min.
(1) Positioning
address
increases if
Phase A leads
Phase B.
(2) Positioning
address
decreases if
Phase B leads
Phase A.
•
Connection examples
Connection of voltage-output manual pulse generator Connection of differential-output manual pulse generator
Signal name Signal name
HA1
HA2
SG
SG
SG
P5
HA2P
HA2N
HB2P
HB2N
SG
P5
A
B
0V
5V
A
B
0V
5V
A
B
SG
HPSEL
A172SENC
A172SENC
Manual pulse
generator side
Manual pulse
generator side
*1*2
*1*2
CAUTION
*1: The 5 VDC power supply from the A172SENC must not be connected if a separate power
supply is used as the manual pulse generator power supply.
If a separate power supply is used as the manual pulse generator power supply, use a 5 V
stabilized power supply. Any other power supply may cause a failure.
*2: Total connector cable length not to exceed 30 m (98.4 ft.)
5V
0V
B
A
A
B
Manual pulse
generator/
synchronous
encoder