DMP Electronics XR2500F Smoke Alarm User Manual


 
XR2500F Installation Guide Digital Monitoring Products
1
IntRoduCtIon
Introduction
1.1 Overview
The DMP XR2500F Addressable Fire Alarm Control Panel (FACP) is an expandable 24 VDC Fire Alarm Control
with built-in DACT and LCD Fire Command Center keyboard with membrane keyswitch. A complete system
can provide:
• 574programmableinputsandoutputsforcommercialandindustrialrealarmservice.
• Eighton-boardgroundedzones
• Twoon-board12VDCClassB,StyeApoweredzones
Connecta12or24VDCregulated,powerlimitedpowersupplylistedforFireProtectiveSignalingSystems
todistributenoticationappliancepowerbetweenthetwoclassBstyleWNACoutputs.AdditionalNAC
outputs can be added with conventional supervision modules or addressable power supply/boosters.
AddressablesmokedetectorsandinputmodulesroundouttheXR2500Ftodeliveratrulyexibleand
expansiveredetectionandnoticationsystem.TheFireAlarmControlPanelisshippedpre-wiredinared
metalenclosurehousingthenecessarycomponentstomonitorandcontrolrealarmnoticationappliances.
Theenclosuredimensionsareasfollows:32”Hx14.5”Wx4”D.Thelidaddsabout0.5”toeachside.
1.2 System Components
TheXR2500FFACPconsistsofthefollowingpre-wiredcomponents:
• OneModelXR2500FCommandProcessorpanel •OneModel893ADualPhoneLinemodule
• TwoModel866ClassBStyleWNACmodules •OneModel630FPCBandmembraneswitch
• One16VAC,56VAtransformer •TwoModel305Plug-inRelays
• OneModel481ZoneExpansionInterfaceCard •OneMetalBackplate
1.3 Power Specications
TransformerInput: Primaryinput:120VAC,60Hz,Secondaryoutput:16VAC56VA
StandbyBattery: 12VDC,1.0AmpsMax.chargingcurrent
Auxiliary: 12 VDC output at 1.0 Amp Max*
BellOutput: 12VDCat.7AmpMax*
Note:ThecombinedAuxiliaryandBelloutputstotalcannotexceed1.9Ampswitha56VATransformer.
All circuits are inherent Power Limited except the red battery wire and AC terminal.
* For Commercial Fire installations, see the Compliance Instructions section.
1.4 Communication
Built-indialerornetworkcommunicationtoDMPModelSCS-1RReceivers
Built-inContactIDcommunicationtonon-DMPreceivers
893ADualPhoneLineModulewithphonelinesupervision
Can operate as a local panel
1.5 Panel Zones
Eight1kOhmEOLburglaryzones(zones1to8).Connectto869ClassAmoduleforburglaryapplications.
Two3.3kOhmEOLpoweredzonewithreset(zones9and10).
Note:UsethesuppliedDMPModel3111kOhmandDMPModel3013.3kOhmresistors.
1.6 Keypad Bus
Youcanconnectupto15ofthefollowingsupervisedkeypadsandexpansionmodulestothekeypadbus:
• AlphanumericFireCommandCentersorkeypads
• Four-and/orsingle-zoneexpansionmodules
• Single-zonedetectors
• Accesscontrolmodules