DMP Electronics XR2500F Smoke Alarm User Manual


 
Digital Monitoring Products XR2500F Installation Guide
38
CoMPlIanCe
35.12 Notication Appliances
ThefollowingtableindicatestheapprovednoticationappliancesthatcanbeusedwiththeXR2500F
system.
Wheelock Model No. Description 12V 24V Max No. of Detectors
using 56 VA
MB-G6-12-R MotorBell,6” X 16
MB-G10-12-R MotorBell,10” X 16
MT-12/24 Multi-toneHorn X X 8
RSS-12575W-F Multi-CandelaStrobe X 5
RSSP-121575W-F Multi-CandelaStrobewithRetrotPlate X 5
SM-12/24-R SyncModule,Singlecircuit X X
DM-12/24-R SyncModule,Dualcircuit X X
MIZ-24 MiniHorn X
AH-24 Horn X
AH-24WP WeatherproofHorn X
MB-G6-24-R 6-InchBell X
MB-G10-24-R 10-InchBell X
RSS-2475C-FW WeatherproofStrobe X
RSS-24MCW-F Multi-CandelaStrobe X
RSSP-24-MCW-F Multi-CandelaStrobewithRetrotPlate X
NS-24MCW-F Multi-CandelaHornStrobe X
AS-24MCW-F Multi-CandelaAudibleStrobe X
ASWP-2475W WeatherproofAudibleStrobe X
35.13 Cross Zoning
Whenusingcrosszoning,theremustbeaminimumoftwodetectorsinstalledineachprotectedspaceand
thedetectorinstallationspacingmustbe0.7timesthelinearspacinginaccordancewithNationalFireAlarm
Code,NFPA72.
35.14 Ground Fault
Forsupervisedcircuits,groundfaultisdetectedat0(zero)Ohms.
Household Fire Warning System Units
ANSI/UL 985, NFPA 72
36.1 Bell Output Denition
TheModelXR2500FpanelBellOutputmustbeprogrammedtooperatesteadyonburglaryalarmsandpulsed
ortemporalonrealarms.
36.2 Audible Devices
Atleastonelistedaudibledeviceratedtooperateoverthevoltagerateof11.7VDCto12.8VDCandrated
at85DBminimummustbeused.
36.3 Auxiliary Circuits
Atleastonerealarminitiatingdeviceshallbeusedonthesystem.Ifthevoltageforthedeviceisapplied
bythecontrolunittherealarminitiatingdeviceshallberatedtooperateovertherangeof11.5VDCto
12.7VDC.
36.4 Bell Cutoff
TheBellCutofftimecannotbelessthanveminutes.