DMP Electronics XR2500F Smoke Alarm User Manual


 
Digital Monitoring Products XR2500F Installation Guide
24
InstallatIon
Dry Contact Relay Outputs
17.1 Description
TheXR2500FpanelprovidestwoprogrammableauxiliarySPDTrelayswiththetwoDMPModel305relaysin
K6(Output1)andK7(Output2)andaModel431OutputHarnessontheJ26-pinHeader.Eachrelayprovides
oneSPDTsetofcontactsthatcanbeoperatedbyanyofthefunctionslistedbelow:
1) Activationbyzonecondition:Steady,Pulsing,Momentary,andFollow
2) Activationby24-hour7-dayschedule:Oneonandoneofftimeadayforeachrelay
3) ManualactivationfromtheSecurityCommandkeypadmenu
4) Communicationfailure
5) Armed area annunciation
6) FireAlarm,FireTrouble,orSupervisory
7) AmbushAlarm
8) ExitandEntrytimers
9) SystemReady
10) Late to Close
RefertotheXR500SeriesProgrammingGuide(LT-0679)forspecicinformation.
17.2 Contact Rating
TheModel305relaycontactsareratedfor1Ampat30VDC(allows.35powerfactor).Connectauxiliary
powertotheRelayOutput1commonterminalbyinstallingthegrayharnesswiretoterminal7.Current
drawforallconnecteddevicesmustnotexceedthepanelmaximumcurrentrating.
17.3 Output Harness Wiring
TheOutputHarnessispre-installedonthe6-pinheaderlabeledJ2.Output2usesthetopthreeprongs,
andOutput1usesthebottomthreeprongs.Outputs1and2arepre-wiredtothe866NACmoduleslocated
withintheXR2500Fenclosure.Forreference,thewireharnessandcontactlocationsareshownbelow:
Contact Color
Output1normallyclosed Violet
Output1common Gray
Output1normallyopen Orange
Output2normallyclosed Blue
Output2common White
Output2normallyopen Yellow