XR2500F Installation Guide Digital Monitoring Products
17
InstallatIon
11.7 XR2500F Standby Battery Calculations
Standby Battery Power Calculations Standby Current Alarm Current
XR2500F Control Panel
Relay Outputs 1-2 (ON)
Switch Grounds 3-6 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Panel Bell Output
Qty ___ 1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
x
x
x
x
x
x
180mA
30mA
5mA
1.6mA
4mA
0.1mA
__180_mA
______
______
______
______
______
Qty ____1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
x
x
x
x
x
x
180mA
30mA
5mA
*2mA
30mA
0.1mA
1500mA
__180_mA
______
______
______
______
______
______mA
893A Dual Phone Line Module Qty ______ x 12mA ______ Qty ______ x 50mA ______
461 Interface Adaptor Card 7mA ______ x 7mA ______
462N Network Interface Card Qty ______ x 50mA ______ Qty ______ x 50mA ______
462P Printer Interface Card Qty ______ x 50mA ______ Qty ______ x 50mA ______
463G Digital Cellular Communicator Card Qty _______ x 21mA ______ Qty _______ x 21mA ______
481 Expansion Interface Card Qty ______ x 15mA ______ Qty ______ x 15mA ______
860 Relay Output Module (one relay active)
All four relays active
Qty _______ x 34mA
138mA
______
______
Qty _______ x 34mA
138mA
______
______
865 Style Y or Z Notication Module Qty ______ x 26mA ______ Qty ______ x 85mA ______
866 Style W Notication Module Qty ______ x 45mA ______ Qty ______ x 76mA ______
867 LX-Bus Style W Notication Module Qty ______ x 30mA ______ Qty ______ x 86mA ______
630F Remote Fire Command Center Qty ______ x 63mA ______ Qty ______ x 92mA ______
690 Security Command Keypad Qty ______ x 77mA ______ Qty ______ x 84mA ______
693/793 Security Command Keypad
Active Zones (EOL Installed)
Qty ______ x 92mA
1.6mA
______
______
Qty ______
Qty ______
x
x
120mA
*2mA
______
______
790 Security Command Keypad
Active Zones (EOL Installed)
Qty ______ x 77mA
1.6mA
______
______
Qty ______
Qty ______
x
x
84mA
*2mA
______
______
7060/7060A/7160 Thinline Keypad Qty ______ x 80mA ______ Qty ______ x 84mA ______
7063/7063A/7163 Thinline Keypad Qty ______ x 86mA ______ Qty ______ x 112mA ______
7070/7070A/7170 Thinline Keypad
Active Zones (EOL Installed)
Qty ______ x 72mA
1.6mA
______
______
Qty ______
Qty ______
x
x
87mA
*2mA
______
______
7073/7073A/7173 Thinline Keypad
Active Zones (EOL Installed)
Qty ______ x 93mA
1.6mA
______
______
Qty ______
Qty ______
x
x
112mA
*2mA
______
______
733 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______
Qty ______
x
x
30mA
1.6mA
______
______
Qty ______
Qty ______
Qty ______
x
x
x
30mA
*2mA
20mA
______
______
______
734 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______
Qty ______
x
x
30mA
1.6mA
______
______
Qty ______
Qty ______
Qty ______
x
x
x
30mA
*2mA
20mA
______
______
______
Copy Sub-Totals to next page Sub-Total Standby
*Basedon10%ofactivezonesinalarm.