DMP Electronics XR2500F Smoke Alarm User Manual


 
XR2500F Installation Guide Digital Monitoring Products
17
InstallatIon
11.7 XR2500F Standby Battery Calculations
Standby Battery Power Calculations Standby Current Alarm Current
XR2500F Control Panel
Relay Outputs 1-2 (ON)
Switch Grounds 3-6 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Panel Bell Output
Qty ___ 1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
x
x
x
x
x
x
180mA
30mA
5mA
1.6mA
4mA
0.1mA
__180_mA
______
______
______
______
______
Qty ____1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
x
x
x
x
x
x
180mA
30mA
5mA
*2mA
30mA
0.1mA
1500mA
__180_mA
______
______
______
______
______
______mA
893A Dual Phone Line Module Qty ______ x 12mA ______ Qty ______ x 50mA ______
461 Interface Adaptor Card 7mA ______ x 7mA ______
462N Network Interface Card Qty ______ x 50mA ______ Qty ______ x 50mA ______
462P Printer Interface Card Qty ______ x 50mA ______ Qty ______ x 50mA ______
463G Digital Cellular Communicator Card Qty _______ x 21mA ______ Qty _______ x 21mA ______
481 Expansion Interface Card Qty ______ x 15mA ______ Qty ______ x 15mA ______
860 Relay Output Module (one relay active)
All four relays active
Qty _______ x 34mA
138mA
______
______
Qty _______ x 34mA
138mA
______
______
865 Style Y or Z Notication Module Qty ______ x 26mA ______ Qty ______ x 85mA ______
866 Style W Notication Module Qty ______ x 45mA ______ Qty ______ x 76mA ______
867 LX-Bus Style W Notication Module Qty ______ x 30mA ______ Qty ______ x 86mA ______
630F Remote Fire Command Center Qty ______ x 63mA ______ Qty ______ x 92mA ______
690 Security Command Keypad Qty ______ x 77mA ______ Qty ______ x 84mA ______
693/793 Security Command Keypad
Active Zones (EOL Installed)
Qty ______ x 92mA
1.6mA
______
______
Qty ______
Qty ______
x
x
120mA
*2mA
______
______
790 Security Command Keypad
Active Zones (EOL Installed)
Qty ______ x 77mA
1.6mA
______
______
Qty ______
Qty ______
x
x
84mA
*2mA
______
______
7060/7060A/7160 Thinline Keypad Qty ______ x 80mA ______ Qty ______ x 84mA ______
7063/7063A/7163 Thinline Keypad Qty ______ x 86mA ______ Qty ______ x 112mA ______
7070/7070A/7170 Thinline Keypad
Active Zones (EOL Installed)
Qty ______ x 72mA
1.6mA
______
______
Qty ______
Qty ______
x
x
87mA
*2mA
______
______
7073/7073A/7173 Thinline Keypad
Active Zones (EOL Installed)
Qty ______ x 93mA
1.6mA
______
______
Qty ______
Qty ______
x
x
112mA
*2mA
______
______
733 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______
Qty ______
x
x
30mA
1.6mA
______
______
Qty ______
Qty ______
Qty ______
x
x
x
30mA
*2mA
20mA
______
______
______
734 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______
Qty ______
x
x
30mA
1.6mA
______
______
Qty ______
Qty ______
Qty ______
x
x
x
30mA
*2mA
20mA
______
______
______
Copy Sub-Totals to next page Sub-Total Standby
*Basedon10%ofactivezonesinalarm.
______mA Sub-Total Alarm ______mA