CoMPlIanCe
Police Station Connected and Local Burglar Alarm Units
ANSI/UL 609
32.1 Mercantile
ForMercantileandPoliceStationConnectoperationtheModelXR500SeriesmustbemountedinanAttack
ResistantHousing,(DMPModel350Aor350H).
32.2 Entry Delay
Themaximumentrydelayusedmustnotbemorethan60secondswhenusingtheModel350Aor350Hhousing.
32.3 Exit Delay
Themaximumexitdelayusedmustnotbemorethan60seconds.
32.4 Bell
AlocalaudiblesignalappliancemustbeusedsuchasAdemcoAB12Mbellandbellhousing.
Inamercantileburglaralarmsystem,amercantilealarmsoundingdevicelocatedwithinabuildingbutoutside
theprotectedarea,isacceptable,provideditisratedforoutsideserviceandalarmconditionsaretransmittedto:
a)Thedispatchlocationofthelawenforcementagencyhavingjurisdictionovertheprotectedpropertyor
b)AcentralstationorresidentialmonitoringstationcomplyingwiththeStandardforCentralStationAlarm
Services,UL827.
Inamercantileburglaralarmsystem,analarmsoundingdevicelocatedwithintheareaofgreatest
protection,oroutsidetheareaofgreatestprotectionbutwithinanareaprotectedbyanalarmsystemand
thatsharesacommoncontrolunitwiththesysteminstalledintheareaofgreatestprotection,isacceptable
provideditisratedforinsideserviceandalarmconditionsaretransmittedto:
a)Thedispatchlocationofthelawenforcementagencyhavingjurisdictionovertheprotectedpropertyor
b)AcentralstationorresidentialmonitoringstationcomplyingwiththeStandardforCentralStationAlarm
Services,UL827.
Aninsidesoundingdeviceshallbemountedatleast10feet(3.05m)abovetheoororatthesurfaceofthe
ceiling.Whenthereisxedconstructionwithintheareathatcouldprovideaccessforanintruder,thealarm
soundingdeviceshallalsobemountedatleast4feet(1.2m),asmeasuredhorizontally,awayfromthe
edgesofthexedconstructionoratleast10feet(3.05m)aboveitsoastominimizeaccessbyanintruder.
32.5 Wireless Audible Annunciation Option
TheWirelessAudibleoptionmustbeselectedasANYforcommercialapplications.
Access Control System Units
ANSI/UL 294
33.1 Panel Designation
TheXR2500Fisdesignatedasastandaloneunit.
33.2 Compatible Devices
ThefollowingdevicesarecompatiblewiththeXR2500Fpanels.
Access Control
733 Wiegand Interface Module Proximity reader connector
734 Wiegand Interface Module Programmable proximity reader connector
OP-08CB Motion Detector Infrared sensor.
* PB-2 REX Button Exit control push button
PP-6005B Proxpoint Plus® Reader Proximity reader
MP-5365 Miniprox® Reader Slimline proximity reader
PR-5455 ProxPro® II Reader Long range reader with sounder
MX-5375 Maxi-Prox™ Reader Long range reader compatible with 1351 Prox Pass
* This device has not been investigated and shall not be used in listed installations.