CoMPlIanCe
California State Fire Marshal Specications
37.1 Bell Output Denition
TheModelXR2500FpanelBellOutputmustbeprogrammedtooperatesteadyonburglaryalarmsandpulsed,
temporal,orCaliforniaSchoolCodeonrealarms.
New York City (MEA) Specications
38.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstalling
theXR500SeriespanelforNewYorkCity(MEA)realarminstallationsthatprovideadigitaldialerwith
networkIPcommunicationasbackup.Firealarminstallationsthatusetwodigitaldialertelephonelinesdo
notneedtocomplywiththesespecications.
38.2 Digital Dialer and Network Communication
Whenusedwithacentralofcecommunicatororatransmitter,theinstallationandoperationofthe
equipmentanddevicesshallcomplywith3RCNY17-01.Theinstallationshallemploythedigitaldialeras
theprimarycommunicator(usingtelephoneline)withnetworkIPcommunicationasbackuporsecondary
meansofcommunication.Itshallhavethecapabilityoftransmittingseparateanddistinctsignalsto
indicatemanualpullstationalarm,automaticdetectionalarm,sprinklerwaterowalarm,supervisorysignal
indications and trouble indications.
38.3 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI,andNFPA70.Allnetworkcablingmustbeinstalledin
accordancewithNFPA70forcommunicationcircuits.
38.4 Communication Programming
Fordigitaldialercommunicationwithsupervisednetworkbackup,programthefollowing:
PRIMARYCOMMTYPE=DD
FIRSTPHONENUMBER=CentralStationReceiverPhoneNumber
BACKUPCOMMTYPE=NET
RECEIVER
ALARMS=YES
38.5 Additional Requirements
ProgramandinstalltheequipmenttocomplywithNFPAbasicrerequirements.RefertotheUniversalFire
AlarmSpecicationsandANSI/UL864,NFPA72inthisdocument.