IntRoduCtIon
Fire Command Center
8.1 Description
TheXR2500FprovidesanLCDdisplayand20-keykeyboardforprogrammingandsystemuseroperation.The
Fire Command Center is installed on the XR2500F enclosure door. A keyswitch is installed and pre-wired
totheleftofthekeyboard.Theusermustturnthekeyswitchtoenablethefourfunctionkeys.Seethe
illustration below.
POWER
TROUBLE
ALARM
COMMAND
1234
5678
90
ABC DEF GHI JKL
MNOPQR STU VWX
YX
ENABLE
SILENCE
RESET
TEST
DRILL
Fire Command Center
Figure 10: Fire Command Center LCD and Keyboard
8.2 Connection
Thedisplayandkeyboardarefactorypre-wiredtotheXR2500Fpanelterminals7,8,9,and10.Forstandby
batterycalculations,thedisplaydraws92mAofcurrentinnormalstandbyoralarmcondition.SeePanel
StandbyBatteryCalculations.Thekeyswitchispre-wiredtothemembranekeyboard.
8.3 Remote Fire Command Center
UptofteenModel630FRemoteFireCommandCentersmayberemotelyattachedtotheXR2500Fsystem.
Seethe630FInstallationGuide(LT-0741)foradditionalinformation.