DMP Electronics XR2500F Smoke Alarm User Manual


 
XR2500F Installation Guide Digital Monitoring Products
33
CoMPlIanCe
31.4 Bell
AlocalaudiblesignalappliancemustbeusedsuchasAdemcoAB12Mbellandbellhousing.
Thealarmhousingforamercantilealarmsystemwithoutaremotealarmtransmissionconnectionshallbe
mountedontheoutsideofthebuilding,visiblefromapublicstreetorhighway.Itshallbeaccessiblefor
examinationandrepair.Itshallalsobelocatednotmorethanfourstoriesabovethestreetlevelunless:
a)Asecondalarmsoundingdeviceandhousing,intendedforoutsideservice,ismountedadjacenttothe
premisesorareaofthebuildinginwhichthealarmsystemisinstalledor
b)Asecondalarmsoundingdevice,intendedforinsideservice,ismountedwithinthepremises.
Ineithercase,theoutsidealarmsoundingdeviceandhousingmaybemountedashighastheseventhoor.
31.5 Bell Cutoff
TheBellCutofftimecannotbelessthan15minutes.
31.6 Automatic Bell Test
TheAutomaticBellTestoptionmustbeprogrammedasYES.
31.7 Standard or Encrypted Line Security
StandardLineSecurityisprovidedwhenconguredasaPath1NETsystemusinganXR500Npaneloran
XR500panelwithaniCOM™NetworkAlarmRouter.TheNETCheck-intimemustbesetto06minutesor
RDM.WhenprogrammedforStandardLineSecurity,ExitTimeRestartisdisabled.Whenadialerisrequired
for06minutecheck-intime,anattackresistantenclosure(DMPModel350A)isrequired.Whenthecheck-in
timeissettoanumberlessthan200seconds,anattackresistantenclosureisnotrequired.
ToprovideEncryptedLinesecurity,installanXR500EpaneloranXR500panelwithaniCOM-E™Encrypted
NetworkAlarmRouter.
ForEncryptedLinesecurityoperation,communicationbetweenthePremiseandSupervisingStationprovides
128bitencryptionwhenusinganXR500EpaneloranXR500panelwithaniCOM-EEncryptedNetworkAlarm
Router.
31.8 Wireless Audible Annunciation Option
TheWirelessAudibleoptionmustbeselectedasANYforcommercialapplications.
31.9 Model 463G CELL Only, Standard or Encrypted Line Security
StandardorEncryptedLineSecurityisprovidedwhenprogrammedusingCELLwithnobackup.XR500
cellularcommunicationisusedasprimarywitha3minutecheck-inwhenarmedordisarmed.
Path 1 programming
CommType:=CELL Checkin:=3minute
Path Type: = Primary FailTime:=3minute
Encrypt:=NOorYES* TestRpt:=NO
SubCode:=NOorYES
*ForEncryptedLineSecurity,programaPassphraseinNetworkOptions.