DMP Electronics XR2500F Smoke Alarm User Manual


 
XR2500F Installation Guide Digital Monitoring Products
37
CoMPlIanCe
Control Units for Fire-Protective Signaling Systems
ANSI/UL 864, NFPA 72
35.1 Power Supply
For listed installations, the total current combined from Auxiliary and Bell Power cannot exceed:
1.2 Amps with a 56 VA transformer; .5 Amp Max for Auxiliary Power and .7 Amp Max for Bell
Combined total current from Terminals 7, 11, 25, and 27 cannot exceed 1.2 Amps.
35.2 Zone Restoral Reports
TheRestoralReportsoptionmustbeselectedasYESorDisarm..
35.3 Power Fail Delay
ThePowerFailDelayoptionmustbeselectedasrequiredbytheserviceofthepanel.ForCentralStationor
RemoteStationservice:1.
35.4 Sprinkler Supervisory
Anyzoneusedforsprinklersupervisorymustbeprogrammedwith“SPRINKLRXXX”asthezonename.The
lastthreecharactersinthezonenamemaybeassignedanumbertoidentifythezone.TheModel893ADual
Phone Line Module must be used on all sprinkler supervisory systems.
35.5 DACT Systems
Twophonelinesmustbeused.Thetwophonelinescannotbegroundstartorpartylines.The893ADual
PhoneLineModuleisusedtoprovidetwophonelineconnectionstothesystem.The2NDPhoneLine
communication option must be selected as DD.
Twodifferentphonenumbersmustbeprogrammedfordigitalcommunication.TheTestTimeoptionmustbe
programmedsothattheXR2500Fsendsareportevery24hours.
35.7 Local Protective Signaling Systems
TheDMPModel865,866,or867NoticationCircuitModulemustbeusedonthebellcircuitfordetectionof
shortsandgrounds.Seethisguideforwiringdiagrams.Anyburglaryorotheroffpremisescommunication
mustbedonewiththeModel893ADualPhoneLineModule.Forlocalcommercialreinstallations,the893A
is required.
35.8 Remote Station Protective Signaling Systems
Youmustprovide60hoursofstandbybattery.Seethisguideforstandbybatterycalculations.Two
RadionicsModelD127ReversingRelayModulesprovidetworeversingpolaritytelephoneconnections.See
theD127InstallationInstructionsheetforwiringdetails.ADMPModel893Aisusedtoprovidetwolinedialer
communication.
35.9 Fire Protective Signaling Systems using Internet/Intranet Networks
TheXR2500FpanelmustbeprogrammedasdescribedbelowforFireProtectiveSignalingSystemsusingNET
Communication Type.
• SUBCODEmustbeprogrammedasYES • FAILTIMEmustbeprogrammedas5
• CHECKINmustbeprogrammedas3 • SENDCOMMTRBLmustbeprogrammedasYES
35.10 Combination Systems
Forcombinationreandburglarysystems,poweredburglarydevices(PIR,Glassbreak,etc.)mustbe
poweredfromaseparatelistedpowersupply(DMPModel505-12).Thisrequirementisnotneededfornon-
poweredburglarydevices(doorcontacts,etc.)whichonlyconnecttothezoneinputofzoneexpandersor
keypads.RefertoPoweredBurglaryDevicesinthisdocument.
Forcombinationreandburglarysystems,burglarysoundingdevicessuchassirensandbellsmustbe
energizedusingpanelrelays,860relays,or716relays.Programmingtheoutputtoactivatetherelaymust
occurusingtheBurglaryBellOutputoptioninAreaInformationorbytheAlarmActionoutputoptionofZone
Information.TheBurglaryBellActionoptionofthepanelBellOptionsmustbeprogrammedasNone.
35.11 Remote Annunciators
AtleastoneModel630FRemoteAnnunciatormustbeusedonthesystem.Allrealarms,retroublesand
supervisoryalarmsortroublesmustbeannunciatedonlyonthe630F.Allburglaryalarmsortroublesmust
onlybeannunciatedonnon-rekeypads.SeeStatusListoptionsoftheXR500SeriesProgrammingGuide
(LT-0679).