Integrated Lighting System w/infiNET
Function name Toggle-Dim Scene (on, 1-15)
Behavior Similar to the “Toggle Scene” function, except that a maintained press
of the button will cause the lights to enter “cycle-dim” mode. That is, all
lights programmed in the specified scene will either raise or lower until
the button is released. (Behavior is the same as Raise Scene function.)
A subsequent maintained button press will cause the lights to dim in the
opposite direction.
If the button is “tapped” instead of held down, it will behave identically to
the “Toggle Scene” function.
LED On when any light in scene is on
Applies To Remote Button
Rocker
Behavior
N/A
Notes This function intended for use only on scenes that do not affect shades.
Function name Open Shades Full (All, Group 1-6)
Behavior Sends the specified shades to Full Open position.
LED On while button is pressed
Applies To Remote Button
Rocker
Behavior
N/A
Notes Shade commands with “All” parameter will only affect all the shade
groups connected to the given CLS-C6RF module. They will not pass
from one CLS-C6RF module to another (either when directly connected
or when linked through a Cresnet system). If you want to open all
shades in a multi-unit system, define a scene to do that.
Function name Close Shades Full (All, Group 1-6)
Behavior Sends the specified shades to Full Closed position.
LED On while button is pressed
Applies To Remote Button
Rocker
Behavior
N/A
Notes Shade commands with “All” parameter will only affect all the shade
groups connected to the given CLS-C6RF module. They will not pass
from one CLS-C6RF module to the other (either when directly
connected or when linked through Cresnet system). If you want to close
all shades in a multi-unit system, define a scene to do that.
Function name Stop Shades (All, Group 1-6)
Behavior Stops the specified shades at current position.
LED On while button is pressed
Applies To Remote Button
Rocker
Behavior
N/A
Notes Shade commands with “All” parameter will only affect all the shade
groups connected to the given CLS-C6RF module. They will not pass
from one CLS-C6RF module to the other (either when directly
connected or when linked through Cresnet system). To accomplish this
function for all shades in a multi-unit system, use SIMPL programming.