Crestron electronic CLS-C6RF Indoor Furnishings User Manual


 
iLux
Integrated Lighting System w/infiNET
Crestron CLS-C6RF
When acquire is done, the display will alternate between “Ac” and result codes.
If acquire was successful, the save led will flash, and the Cancel led will turn
off. (Cancel button is disabled). Press the Save button to go into Standard
mode.
If acquire was unsuccessful, the Cancel led will flash. The previous gateway
link information will be restored. Press the Cancel button to go into Standard
mode.
Result codes:
“00” = Successful
“E1” = Cannot communicate with the transceiver
“E2” = Search expired; no gateway found
“E3” = RF channel is disabled. This code is immediately shown when the Acquire
mode is entered.
“E4” = Invalid EUID or EUID was not assigned
Unacquire Gateway (UA)
This procedure is used to unacquire the C2N-MNETGW gateway.
To do this, enter Setup mode and scroll to the “UA” option, using the ^ and v
buttons.
Press and hold the up/down button for five seconds. The “UA.” text will flash,
the Save and Cancel leds will flash.
If “Unacquire” is successful, the Save led will flash. The display will alternate
between “UA” and the passed result code. Press the Save button to end Setup
mode and enter Standard mode
If “Unacquire” is unsuccessful, the Cancel led will flash. The display will
alternate between “UA” and the failed result code. Press the Cancel button to
end Setup mode and enter Standard mode.
Result codes:
“00” = Successful
“E1” = Cannot communicate with the transceiver
“E2” = Unacquire failed (1-was never acquired, 2-etc.)
Display/Set RF Channel
This procedure is used to display or set the RF Channel.
To do this, enter Setup mode and scroll to the “Ch” option, using the ^ and v
buttons.
Press the master up or down key. The current channel is shown. The Channel
mode is now locked. A dot will be shown to the right of the “Ch”. The display
will alternate between “Ch.” and the current channel.
If the button is held for more than ½ second, the unit will auto-repeat and start
scrolling through the values. At the upper or lower limit, the unit will pause for
½ second and then wrap around.
Use the up/down key to change channel. If held for more than ½ seconds will
auto repeat. At limit will pause for ½ second and then wrap around
Press the Save button to save the new value and return to Standard mode.