Xantrex Technology Freedom SW Series Home Security System User Manual


 
Configuration
3–12 975-0704-01-01 Revision A
To connect the Conext ComBox to an existing Xanbus network:
The assumption at this point is that there is an existing Xanbus network and all
Xanbus-enabled devices in that network have been previously interconnected
with each other.
1. Put the Freedom SW inverter/chargers and Xanbus AGS into standby mode
before connecting the Conext ComBox to avoid triggering any unintentional
time-based events.
You can put the inverter/chargers out of standby mode later when you have
completed configuration of the Conext ComBox.
2. Using the sample illustration below, connect the Conext ComBox to the
Xanbus network.
Be sure to terminate the Xanbus network with Xanbus network terminators at both
ends.
NOTICE
EQUIPMENT DAMAGE
Do not connect a Xanbus RJ-45 cable plug into the 10/100 Ethernet port of the
Conext ComBox.
Failure to follow these instructions can damage equipment or affect
network performance.