Mitsubishi Electronics FX3GC Garage Door Opener User Manual


 
892
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.3 Supplementary Explanation of Devices for Error Detection
38.3.2 Operations of special devices for error detection
Special auxiliary relays for error detection and special data registers for error detection operate in the relationship
shown below.
The state of error occurrence can be checked by monitoring the contents of auxiliary relays and data registers or by
using the PLC diagnosis function programming tool.
38.3.3 Error detection timing
Error item
ERROR (ERR)
LED status
The status of the PLC
after error detection
Error detection timing
When power is
turned from
OFF to ON
When PLC mode
switches from
STOP to RUN
Other timing
M8060 I/O configuration error Unlit
RUN/STOP is Continued
Check Check
M8061 PLC hardware error Lit Forced STOP Check Always
M8062 Serial communication error 0 [ch 0] Unlit
RUN/STOP is Continued
⎯⎯
When receiving signal
from counterpart station
M8063 Serial communication error 1 [ch 1] Unlit
RUN/STOP is Continued
⎯⎯
When receiving signal
from counterpart station
M8438 Serial communication error 2 [ch 2] Unlit
RUN/STOP is Continued
⎯⎯
When receiving signal
from counterpart station
M8064 Parameter error Flickering
STOP is Continued
Check Check
When program is changed
(STOP)
When program is
transferred (STOP)
M8065 Syntax error Flickering
STOP is Continued
M8066 Circuit error Flickering
STOP is Continued
M8067 Operation error Unlit
RUN is Continued
⎯⎯RUN mode
M8068 Operation error latch Unlit
RUN is Continued
M8109 I/O refresh error Unlit
RUN/STOP is Continued
⎯⎯Always
M8316 Unconnected I/O designation error Unlit
RUN is Continued
⎯⎯RUN mode
M8318 BFM initialization failure Unlit
RUN is Continued
Check
M8449 Special block error Unlit
RUN/STOP is Continued
⎯⎯Always
M8487 USB communication error [USB] Unlit
RUN/STOP is Continued
⎯⎯
When receiving signal
from counterpart station
M8489 Special parameter error Unlit
STOP is Continued
Check
When special parameter
is changed (STOP)
D8166 Special block error condition Unlit
RUN/STOP is Continued
⎯⎯Always
M8069
I/O
bus check
By using the PLC diagnosis function provided in the programming tool (GX Works2, etc.), Graphic
Operation Terminal (GOT1000) or the display module (FX
3U
-7DM), the contents of the error code
(D8060 to D8067, D8438, D8449) can be checked in message format.
ON when an error
occurs
Special M number
(smallest device
number) of error
occurrence
After clearing errors, forcibly clear M8068 using the device monitor function in a programming tool.
D8009 M8009 24V DC down
D8060 M8060 I/O configuration error
D8061 M8061 PLC hardware error
D8063 M8063 Serial communication error 1
D8438 M8438 Serial communication error 2
D8064 M8064 Parameter error
D8065 M8065 Syntax error
D8066 M8066 Circuit error
D8067 M8067 Operation error
M8068 Operation error latch
D8004
M8004
D8313
32K Error step number
The error step number is also stored in
D8069, but only for programs 32K
steps and less.
1st error step latched
The error step number is also stored in
D8068, but only for programs 32K
steps and less.
D8317
M8316 Unconnected I/O
designation error
D8316
D8314D8315
D8312
Error step number
D8487
D8449
D8489
M8487
M8449
M8489
USB communication error
Special block error
Special parameter error
M8318 BFM initialization failure
D8318
D8319
Error unit number
Error BFM number
D8062 M8062 Serial communication error 0