Trane RTAC 140-400 ton units (50 HZ) Air Conditioner User Manual


 
70 RTAC-SVX01F-EN
Installation - Electrical
RTAC
400
200/60/3 1 NA
200/60/3 2 931/931 1200/1200 1200/1200 4 373/373/
373/373
2156/2156/
2156/2156
701/701/
701/701
14/14
1. 5 6 . 5
1. 5 9
230/60/3 1 NA
230/60/3 2 820/820 1000/1000 1000/1000 4 324/324/
324/324
1756/1756/
1756/1756
571/571/
571/571
14/14
1. 5 6 . 5
1. 5 9
380/60/3 1 NA
380/60/3 2 490/490 600/600 600/600 4 196/196/
196/196
1060/1060/
1060/1060
345/345/
345/345
14/14
1. 5 3 . 5
1. 5 9
460/60/3 1 773 800 800 4 162-162-
162-162
878-878-878-
878
285-285-
285-285
28
1. 5 3 . 0
1. 5 9
460/60/3 2 407/407 500/500 450/450 4 162/162/
162/162
878/878/878/
878
285/285/
285/285
14/14
1. 5 3 . 0
1. 5 9
575/60/3 1 623 700 700 4 130-130-
130-130
705-705-705-
705
229-229-
229-229
28
1. 5 2 . 5
1. 5 9
575/60/3 2 328/328 450/450 400/400 4 130/130/
130/130
705/705/705/
705
229/229/
229/229
14/14
1. 5 2 . 5
1. 5 9
400/50/3 1 882 1000 1000 4 189-189-
189-189
1089-1089-
1089-1089
354-354-
354-354
28
0.9 2.8
1. 5 9
400/50/3 2 465/465 600/600 600/600 4 189/189/
189/189
1089/1089/
1089/1089
354/354/
354/354
14/14
0.9 2.8
1. 5 9
Notes:
1. As standard, 140-250 ton (60 Hz) units and 140-200 ton (50Hz) units have a single point power connection. Optional dual point power connections
are available. As standard, 275-500 ton (60Hz) units and 250-400 ton (50Hz) units have dual point power connections. Optional single point power
connections are available on 380V, 460V 575V/50 Hz and 400V/50 Hz units.
2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the
condenser fan FLA per NEC 440-22. (Use FLA per circuit, NOT FLA for the entire unit).
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the
condenser fans FLAs per NEC 440-33.
4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second
compressor RLA and the sum of the condenser fan FLAs.
5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995.
6. Local codes may take precedence.
7. Control VA includes operational controls only. Does not include evaporator heaters.
8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
9. Voltage Utilization Range:
Rated Voltage 200/60/3 230/60/3 380/60/3 460/60/3 575/60/3 400/50/3
Use Range 180-220 208-254 342-418 414-506 516-633 360-440
10. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is required to power the evaporator heaters (1640 watts).
11. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP).
Table 18 Unit Electrical Data for High Efficiency at Std. Ambient Operation
Unit
Size
Rated
Voltage
Unit Wiring Motor Data
# of
Power
Conns
(1)
MCA (3)
Ckt1/
Ckt2
Max. Fuse,
HACR
Breaker or
MOP (11)
Ckt1/Ckt2
Rec. Time
Delay or
RDE (4)
Ckt1/Ckt 2
Compressor (Each) Fans (Each)
Qty
RLA (5)
Ckt1/Ckt2
XLRA (8)
Ckt1/Ckt2
YLRA (8)
Ckt1/Ckt2
Qty.
Ckt1/Ckt2 kW FLA
Control
VA (7)