36 RTAC-SVX01F-EN
Installation - Mechanical
Isolation and Sound Emission
The most effective form of isolation is to locate the unit away from any sound sensi-
tive area. Structurally transmitted sound can be reduced by elastomeric vibration elim-
inators. Spring isolators are not recommended. Consult an acoustical engineer in
critical sound applications.
For maximum isolation effect, isolate water lines and electrical conduit. Wall sleeves
and rubber isolated piping hangers can be used to reduce the sound transmitted
through water piping. To reduce the sound transmitted through electrical conduit, use
flexible electrical conduit.
State and local codes on sound emissions should always be considered. Since the
environment in which a sound source is located affects sound pressure, unit place
-
ment must be carefully evaluated. Sound power levels for Trane air-cooled Series R
®
chillers are available on request.
Figure 17 Unit Isolator Locations
200 Ton 60 Hz Std Eff 3528 3974 3007 3453 NA NA NA NA 13962 107 45
1600 1802 1364 1566 6333 2710 1140
225 Ton 60 Hz Std Eff 4031 4600 3473 4042 NA NA NA NA 16145 125 45
1828 2086 1575 1833 7323 3167 1148
250 Ton 60 Hz Std Eff 4092 4615 3527 4050 NA NA NA NA 16284 125 45
1856 2094 1600 1837 7386 3167 1140
Table 6 Lifting Weights and CG Dimensions (Refer to Figure 14 - Figure 15)
Unit
W1 W2 W3 W4 W5 W6 W7 W8 Shipping
Weight
Xcg Ycg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
in
mm
in
mm
Table 7 Remote Evaporator Lifting Weights
140 155 170 185 200 225 250 140 155 170 185 200
2487
1128
2525
1145
2528
1146
2556
1159
2600
1179
2797
1268
2846
1291
2528
114 6
2556
115 9
2600
1179
2797
1268
2846
1291