Trane RTAC 140-400 ton units (50 HZ) Air Conditioner User Manual


 
66 RTAC-SVX01F-EN
Installation - Electrical
RTAC
450
200/60/3 1 NA
200/60/3 2 1124/947 1200/1200 1200/1200 4 459/459/386/
386
2525/2525/2156/
2156
821/821/701/
701
14/12 1.5 6.5 1.59
230/60/3 1 NA
230/60/3 2 989/834 1200/1000 1200/1000 4 399/399/336/
336
2126/2126/1756/
1756
691/691/571/
571
14/12 1.5 6.5 1.59
380/60/3 1 NA
380/60/3 2 594/499 800/700 700/600 4 242/242/203/
203
1306/1306/1060/
1060
424/424/345/
345
14/12 1.5 3.5 1.59
460/60/3 1 864 1000 1000 4 200-200-168-
168
1065-1065-878-878 346-346-285-
285
26 1.5 3.0 1.59
460/60/3 2 492/414 600/500 600/500 4 200/200/168/
168
1065/1065/878/878 346/346/285/
285
14/12 1.5 3.0 1.59
575/60/3 1 693 800 800 4 160-160-134-
134
853-853-705-705 277-277-229-
229
26 1.5 2.5 1.59
575/60/3 2 395/332 500/450 450/400 4 160/160/134/
134
853/853/705/705 277/277/229/
229
14/12 1.5 2.5 1.59
RTAC
500
200/60/3 1 NA
200/60/3 2 1124/1124 1200/1200 1200/1200 4 459/459/459/
459
2525/2525/2525/
2525
821/821/821/
821
14/14 1.5 6.5 1.59
230/60/3 1 NA
230/60/3 2 989/989 1200/1200 1200/1200 4 399/399/399/
399
2126/2126/2126/
2126
691/691/691/
691
14/14 1.5 6.5 1.59
380/60/3 1 NA
380/60/3 2 594/594 800/800 700/700 4 242/242/242/
242
1306/1306/1306/
1306
424/424/424/
424
14/14 1.5 3.5 1.59
460/60/3 1 929 1000 1000 4 200-200-200-
200
1065-1065-1065-
1065
346-346-346-
346
28 1.5 3.0 1.59
460/60/3 2 490/490 600/600 600/600 4 200/200/200/
200
1065/1065/1065/
1065
346/346/346/
346
14/14 1.5 3.0 1.59
575/60/3 1 745 800 800 4 160-160-160-
160
853-853-853-853 277-277-277-
277
28 1.5 2.5 1.59
575/60/3 2 393/393 500/500 450/450 4 160/160/160/
160
853/853/853/853 277/277/277/
277
14/14 1.5 2.5 1.59
Notes:
1. As standard, 140-250 ton (60 Hz) units and 140-200 ton (50Hz) units have a single point power connection. Optional dual point power connections
are available. As standard, 275-500 ton (60Hz) units and 250-400 ton (50Hz) units have dual point power connections. Optional single point power
connections are available on 380V, 460V 575V/50 Hz and 400V/50 Hz units.
2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the
condenser fan FLA per NEC 440-22. (Use FLA per circuit, NOT FLA for the entire unit).
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the
condenser fans FLAs per NEC 440-33.
4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second
compressor RLA and the sum of the condenser fan FLAs.
5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995.
6. Local codes may take precedence.
7. Control VA includes operational controls only. Does not include evaporator heaters.
8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
9. Voltage Utilization Range:
Rated Voltage 200/60/3 230/60/3 380/60/3 460/60/3 575/60/3 400/50/3
Use Range 180-220 208-254 342-418 414-506 516-633 360-440
10. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is required to power the evaporator heaters (1640 watts).
11. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP).
Table 17 Unit Electrical Data for Std. Efficiency at All Ambient Operation
Unit
Size
Rated
Voltage
Unit Wiring Motor Data
# of
Power
Conns
(1)
MCA (3)
Ckt1/Ckt2
Max. Fuse,
HACR
Breaker or
MOP (11)
Ckt1/Ckt2
Rec. Time
Delay or
RDE (4)
Ckt1/Ckt2
Compressor (Each) Fans (Each)
Qty
RLA (5)
Ckt1/Ckt2
XLRA (8)
Ckt1/Ckt2
YLRA (8)
Ckt1/Ckt2
Qty.
Ckt1/Ckt2 kW FLA
Control
VA (7)