Controls Interface
Setpoint Screen
The setpoint screen is a two-part screen. Screen 1 lists all setpoints available to
change along with their current value. The operator selects a setpoint to change by
touching either the verbal description or setpoint value. Doing this causes the screen
to switch to Screen 2.
In Screen 1 the language setpoint will always be the last setpoint in the list. This will
facilitate language changes by placing that control in a standard position across all
CH.530 product lines.
Screen 2 displays the current value of the chosen setpoint in the upper ½ of the dis-
play. It is displayed in a changeable format consistent with its type. Binary setpoints
are considered to be simple two state enumeration and will use radio buttons. Ana
-
log setpoints are displayed as spin buttons. The lower half of the screen is reserved
for help screens.
Auto Stop
Rfgt
Setpoint Diagnostic
Auto Local or Remote:
Front Panel Chilled Water Setpoint:
Local
Condenser Limit Setpt: XXX % HPC
Front Panel Current Limit Setpoint:
Low Ambient Lockout Setpt: 35.0 F
Low Ambient Lockout: Enable
44.0 F
100 %
Table 30 Refrigerant Screen
Description Resolution Units
Cond Rfgt Pressure Ckt1/Ckt2 X.X Pressure
Sat Cond Rfgt Temp Ckt1/Ckt2 X.X F / C
Evap Rfgt Pressure Ckt1/Ckt2 X.X Pressure
Sat Evap Rfgt Temp Ckt1/Ckt2 X.X F / C
Evap Approach Temp Ckt1/Ckt2 X.X F / C
Rfgt Liquid Level Ckt1/Ckt2 X.X Height
Table 31 Setpoint Screen
Description Resolution or Text Units
Auto Local or Remote Remote/Local Text
Front Panel Chilled Water Setpoint X.X F / C
Front Panel Current Limit Setpoint XXX % RLA
Differential to Start X.X Temperature
Differential to Stop X.X Temperature
Condenser Limit Setpoint Enable/Disable Text
Low Ambient Lockout Setpoint X.X Temperature
Low Ambient Lockout Enable/Disable Text
Ice Build Enable/Disable Text
Front Panel Ice Termination Setpoint X.X Temperature