Trane RTAC 140-400 ton units (50 HZ) Air Conditioner User Manual


 
RTAC-SVX01F-EN 121
Te ch Vi ew
Features Installation Accessories N - No installation accessories
R - Neoprene Isolators
F - Flanged water connection kit
G - Neoprene isolators and flange wtr conn kit
Factory Test 0 - No factory run test
Control, Label, and
Literature Language
E - English
G - Chinese
Special Order X - Standard catalog configuration
S - Unit has special order feature
Custom Comm 3 ICD address 55 1-64
REM = C
Status Relay #1 J2-10,11,12 Alarm - Latching None, Alarm - Latching (Active diagnostic
persistence latching), Alarm - Auto reset (Active
diagnostic persistence non-latching), Alarm
(Active diagnostic persistence latching or non-
latching), Alarm Ckt1 (Active diagnostic
persistence latching or non-latching), Alarm Ckt2
(Active diagnostic persistence latching or non-
latching), Chiller Limit Mode (With 20 minute
filter), Circuit 1 Running, Circuit 2 Running,
Maximum Capacity
COOP = A, D or X
Status Relay #2 J2-7,8,9 Chiller Running
Status Relay #3 J2-4,5,6 Maximum Capacity
Status Relay #4 J2-1,2,3 Chiller Limit Mode
Phase Unbalance Trip 30 10-50%
Phase Unbalance Grace
Period
90 30-255 Sec
Maximum Acceleration
Time
31-255 Sec
Starter Feature All Enabled Contactor Integrity Test, Phase Reversal Detect,
Phase Unbalance Detect
External Chilled Water
Setpoint Detection
2-10 VDC 2-10 VDC, 4-20 mA
CIOP = C or B
External Current Limit Water
Setpoint Detection
2-10 VDC 2-10 VDC, 4-20 mA
CIOP = C or B
Custom Unit Voltage 400 380,400,415
VOLT = D
Nameplate The Model Number field contains the model number stored in the EasyView or DynaView.
The Confirm Code field contains the confirm code stored in the EasyView or DynaView. The
confirm code is a four-digit hex value that is a mathematical calculation of the model number. This
number has one to one correlation to a specific model number and is used to verify that the model
number was entered properly.
The Serial Number field contains the serial number stored in the EasyView or DynaView.
This model number and confirmation code must be know when the main processor requires
replacement.
Table 36 Configuration View Items
Tab Item Default Description