Trane RTAC 140-400 ton units (50 HZ) Air Conditioner User Manual


 
RTAC-SVX01F-EN 133
Diagnostics
19D Phase Loss - Compressor 1B Immediate Latch Same as Phase Loss - Compressor 1A Local
19E Phase Loss - Compressor 2A Immediate Latch Same as Phase Loss - Compressor 1A Local
19F Phase Loss - Compressor 2B Immediate Latch Same as Phase Loss - Compressor 1A Local
184 Phase Reversal -
Compressor 1A
Immediate Latch A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip in a
maximum of .3 second from compressor start.
Local
185 Phase Reversal -
Compressor 1B
Immediate Latch Same as Phase Reversal - Compressor 1A Local
186 Phase Reversal -
Compressor 2A
Immediate Latch Same as Phase Reversal - Compressor 1A Local
187 Phase Reversal -
Compressor 2B
Immediate Latch Same as Phase Reversal - Compressor 1A Local
1A0 Power Loss - Compressor 1A Immediate NonLatch The compressor had previously established currents while running and
then all three phases of current were lost. Design: Less than 10% RLA,
trip in 2.64 seconds. This diagnostic will preclude the Phase Loss
Diagnostic and the Transition Complete Input Opened Diagnostic from
being called out. To prevent this diagnostic from occurring with the
intended disconnect of main power, the minimum time to trip must be
greater than the guaranteed reset time of the Starter module. Note:
This diagnostic prevents nuisance latching diagnostics due to a
momentary power loss - It does not protect motor/compressor from
uncontrolled power reapplication. See Momentary Power Loss
Diagnostic for this protection. This diagnostic is not active during the
start mode before the transition complete input is proven. Thus a
random power loss during a start would result in either a "Starter Fault
Type 3" or a "Starter Did Not Transition" latching diagnostic.
Remote
1A1 Power Loss - Compressor 1B Immediate NonLatch Same as Power Loss - Compressor 1A Remote
1A2 Power Loss - Compressor 2A Immediate NonLatch Same as Power Loss - Compressor 1A Remote
1A3 Power Loss - Compressor 2B Immediate NonLatch Same as Power Loss - Compressor 1A Remote
8C Pumpdown Terminated -
Circuit 1
Info NonLatch The pumpdown cycle for this circuit was terminated abnormally due to
excessive time or due to a specific set of diagnostic criteria - but w/o
associated latching diagnostics
Remote
8D Pumpdown Terminated -
Circuit 2
Info NonLatch Same as Pumpdown Terminated - Circuit 1 Remote
1B2 Severe Current Imbalance -
Compressor 1A
Immediate Latch A 30% Current Imbalance has been detected on one phase relative to
the average of all 3 phases for 90 continuous seconds.
Local
1B3 Severe Current Imbalance -
Compressor 1B
Immediate Latch Same as Severe Current Imbalance - Compressor 1A Local
1B4 Severe Current Imbalance -
Compressor 2A
Immediate Latch Same as Severe Current Imbalance - Compressor 1A Local
1B5 Severe Current Imbalance -
Compressor 2B
Immediate Latch Same as Severe Current Imbalance - Compressor 1A Local
5CD Starter 1A Comm Loss: MP Immediate Latch Starter has had a loss of communication with the MP for a 15 second
period.
Local
6A7 Starter 1A Dry Run Test Immediate Latch While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was sensed
at the Current Transformers.
Local
5CE Starter 1B Comm Loss: MP Immediate Latch Starter has had a loss of communication with the MP for a 15 second
period.
Local
6A8 Starter 1B Dry Run Test Immediate Latch While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was sensed
at the Current Transformers.
Local
5CF Starter 2A Comm Loss: MP Immediate Latch Starter has had a loss of communication with the MP for a 15 second
period.
Local
6A9 Starter 2A Dry Run Test Immediate Latch While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was sensed
at the Current Transformers.
Local
5D0 Starter 2B Comm Loss: MP Immediate Latch Starter has had a loss of communication with the MP for a 15 second
period.
Local
6AA Starter 2B Dry Run Test Immediate Latch While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was sensed
at the Current Transformers.
Local
Hex
Code
Diagnostic Name
and Source
Severity Persis-
tence
Criteria Reset
Level