Omron FQM1-MMA21 Home Security System User Manual


 
143
Input Interrupts Section 7-3
Counter Mode
7-3-5 Using Input Interrupts
Input Interrupt Mode Procedure
1,2,3... 1. Determine which input interrupt number will be used.
2. Wire the input.
3. Make the necessary System Setup settings.
Set the Interrupt Input Settings (set whether an interrupt will be generated
when the input turns ON, OFF, or both).
Note The default input setting is for a normal input.
4. Create the necessary ladder programming.
• Use the MSKS(690) instruction (SET INTERRUPT MASK) to enable the
input as an interrupt input.
Create the interrupt task program.
Item Specification
Interrupt condition Counter decremented from SV each time input contacts 0 to 3
(CIO 0000.00 to CIO 0000.03) turn ON, OFF, or both and PV
reaches 0.
Note Set the interrupt condition in the System Setup.
Interrupt task num-
bers
CIO 0000.00 to CIO 0000.03: Interrupt tasks 000 to 003
(fixed)
Counter operation Decrementing pulse input
Input method Single phase
Counting speed 2 kHz
Counter value 0000 to FFFF hex
Counter PV storage Input interrupts 0 to 3 (CIO 0000.00 to CIO 0000.03):
A524 to A527
Counter SV storage Input interrupts 0 to 3 (CIO 0000.00 to CIO 0000.03):
A520 to A523
Input Allocated input bit Interrupt task number
External interrupt input 0 CIO 0000.00 000
External interrupt input 1 CIO 0000.01 001
External interrupt input 2 CIO 0000.02 002
External interrupt input 3 CIO 0000.03 003
Interrupt
input
0 CIO 0000.00
1
CIO 0000.01
2
CIO 0000.02
3
CIO 0000.03
Interrupt input 0
MSKS Interrupt control
Enable interrupt inputs
Ladder program
Interrupt input
settings
System Setup
Interrupt generated.
Execute specified task.
END
Interrupt input 1
Interrupt input 2
Interrupt input 3