Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
80 Johnson Controls Unitary Products
J10NC/NDC00D, J15NC/NDC00D
3.0
208-3-60 9.6
None --- --- --- 12.0 15
10 KW 7.5 1 20.8 38.1 40
16 KW 12 2 33.4 53.7 60
26 KW 19.5 2 54.2 79.8 80
36 KW 27 2 75.1 105.8 110
50 KW
4
37.6 2 104.2 116.2 125
230-3-60 9.4
None --- --- --- 11.8 15
10 KW 10 1 24.1 41.8 45
16 KW 16 2 38.5 59.9 60
26 KW 26 2 62.5 89.9 90
36 KW 36 2 86.6 120.0 125
50 KW
4
50 2 120.3 132.0 150
460-3-60 4.7
None --- --- --- 5.9 15
10 KW 10 1 12.0 20.9 25
16 KW 16 2 19.2 29.9 30
26 KW 26 2 31.3 45.0 45
36 KW 36 2 43.3 60.0 70
50 KW
4
50 2 60.1 66.0 70
575-3-60 3.6
None --- --- --- 4.5 15
10 KW 10 1 9.6 16.5 20
16 KW 16 2 15.4 23.7 25
26 KW 26 2 25.0 35.8 40
36 KW 36 2 34.6 47.8 50
50 KW
4
50 2 48.1 52.6 60
J15NC/NDC00E
5.0
208-3-60 14.0
None --- --- --- 17.5 20
10 KW 7.5 1 20.8 43.6 45
16 KW 12 2 33.4 59.2 60
26 KW 19.5 2 54.2 85.3 90
36 KW 27 2 75.1 111.3 125
50 KW 37.6 2 104.2 121.7 125
230-3-60 14.0
None --- --- --- 17.5 20
10 KW 10 1 24.1 47.6 50
16 KW 16 2 38.5 65.6 70
26 KW 26 2 62.5 95.7 100
36 KW 36 2 86.6 125.8 150
50 KW 50 2 120.3 137.8 150
460-3-60 7.0
None --- --- --- 8.8 15
10 KW 10 1 12.0 23.8 25
16 KW 16 2 19.2 32.8 35
26 KW 26 2 31.3 47.8 50
36 KW 36 2 43.3 62.9 70
50 KW 50 2 60.1 68.9 70
575-3-60 5.2
None --- --- --- 6.5 15
10 KW 10 1 9.6 18.5 20
16 KW 16 2 15.4 25.7 30
26 KW 26 2 25.0 37.8 40
36 KW 36 2 34.6 49.8 50
50 KW 50 2 48.1 54.6 60
Electrical Data - Indoor Units (Continued)
Motor HP Power Supply
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
FLA Model KW Stages Amps