115°F 125°F
4500
77 175.1 18.3 92.4 73.5 54.6 - - - 157.4 19.9 85.8 67.0 48.1 - - -
72 162.0 18.1 120.0 101.1 82.2 63.3 - - 146.7 19.8 114.3 95.5 76.6 57.8 - -
67 148.8 18.0 147.6 128.7 109.8 91.0 72.1 - 136.1 19.6 136.1 124.0 105.1 86.3 67.4 -
62 138.1 17.8 138.1 138.1 134.4 115.5 96.6 77.7 126.2 19.5 126.2 126.2 126.2 107.5 88.6 69.7
57 143.6 17.8 143.6 143.6 126.1 107.2 88.3 69.4 132.1 19.6 132.1 132.1 114.2 95.4 76.5 57.6
5250
77 179.2 18.3 112.3 80.6 58.9 - - - 161.8 19.9 110.6 74.3 52.6 - - -
72 165.7 18.1 132.0 110.4 88.7 67.1 - - 150.8 19.8 126.9 105.3 83.6 62.0 - -
67 152.3 18.0 151.7 140.2 118.6 96.9 75.3 - 139.9 19.6 139.9 136.3 114.7 93.0 71.4 -
62 141.3 17.8 141.3 141.3 145.0 123.4 101.7 80.1 129.7 19.5 129.7 129.7 129.7 116.6 94.6 72.9
57 146.9 17.8 146.9 146.9 136.1 114.4 92.8 71.1 135.7 19.6 135.7 135.7 124.8 103.6 81.5 59.9
6000
77 183.2 18.3 132.3 87.6 63.3 - - - 166.2 19.9 135.3 81.5 57.1 - - -
72 169.5 18.1 144.0 119.6 95.3 70.9 - - 154.9 19.8 139.5 115.1 90.6 66.2 - -
67 155.8 18.0 155.8 151.6 127.3 102.9 78.5 - 143.6 19.6 143.6 143.6 124.2 99.8 75.4 -
62 144.5 17.8 144.5 144.5 155.7 131.3 106.9 82.5 133.2 19.5 133.2 133.2 133.2 125.8 100.5 76.1
57 150.2 17.9 150.2 150.2 146.0 121.6 97.3 72.9 139.4 19.6 139.4 139.4 135.3 111.9 86.5 62.1
6750
72 171.9 18.2 155.2 128.6 102.0 75.4 - - 156.4 19.8 149.5 122.9 96.3 69.7 - -
67 158.0 18.0 158.0 155.9 136.3 109.7 83.1 - 145.1 19.7 145.1 145.1 132.0 105.4 78.8 -
62 146.6 17.8 146.6 146.6 152.1 125.6 99.0 72.4 134.5 19.5 134.5 134.5 134.5 116.4 89.4 62.7
57 152.4 17.9 152.4 152.4 150.3 123.7 97.1 70.5 140.8 19.6 140.8 140.8 138.8 112.7 85.5 58.9
7500
72 174.3 18.2 166.3 137.5 108.8 80.0 - - 158.0 19.9 158.0 130.8 102.0 73.2 - -
67 160.2 18.1 160.2 160.2 145.3 116.5 87.7 - 146.5 19.8 146.5 146.5 139.9 111.1 82.3 -
62 148.6 17.9 148.6 148.6 148.6 119.8 91.0 62.3 135.8 19.6 135.8 135.8 135.8 107.0 78.2 49.4
57 154.5 18.0 154.5 154.5 154.5 125.7 96.9 68.1 142.2 19.7 142.2 142.2 142.2 113.4 84.6 55.8
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor
J15PC/J15NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65