Johnson Controls R-410A Heat Pump User Manual


 
505429-JTG-F-1010
Johnson Controls Unitary Products 47
115°F 125°F
7500
77 317.1 31.5 143.2 111.6 79.9 - - - 308.6 34.3 138.7 107.1 75.4 - - -
72 288.5 30.8 194.6 163.0 131.4 99.7 - - 276.2 33.7 188.8 157.2 125.5 93.9 - -
67 259.8 30.2 246.1 214.4 182.8 151.2 119.5 - 243.8 33.1 238.9 207.2 175.6 144.0 112.4 -
62 246.4 29.7 246.4 235.1 203.5 171.8 140.2 108.6 226.6 32.4 226.6 219.0 187.4 155.7 124.1 92.5
57 258.8 29.6 258.8 238.8 207.2 175.5 143.9 112.3 243.9 32.3 243.9 221.9 190.3 158.6 127.0 95.4
8750
77 318.9 31.6 180.8 124.6 88.5 - - - 309.5 34.7 183.9 120.7 84.5 - - -
72 290.1 31.0 217.6 181.5 145.4 109.2 - - 277.0 34.0 212.9 176.7 140.6 104.4 - -
67 261.3 30.4 254.4 238.4 202.3 166.1 130.0 - 244.4 33.4 242.0 232.8 196.6 160.4 124.2 -
62 247.8 29.9 247.8 242.1 225.1 189.0 152.9 116.7 227.2 32.6 227.2 223.4 210.1 174.7 137.7 101.5
57 260.2 29.7 260.2 250.2 229.2 193.1 157.0 120.9 244.6 32.6 244.6 233.5 213.3 178.0 140.9 104.7
10000
77 320.7 31.8 218.4 137.6 97.0 - - - 310.4 35.0 229.1 134.3 93.6 - - -
72 291.7 31.2 240.6 200.0 159.3 118.7 - - 277.7 34.3 237.1 196.3 155.6 114.8 - -
67 262.7 30.5 262.7 262.3 221.7 181.1 140.5 - 245.1 33.7 245.1 245.1 217.6 176.8 136.1 -
62 249.2 30.0 249.2 249.2 246.8 206.1 165.5 124.9 227.8 32.9 227.8 227.8 227.8 193.6 151.2 110.4
57 261.7 29.9 261.7 261.7 251.3 210.7 170.0 129.4 245.2 32.9 245.2 245.2 236.3 197.4 154.8 114.1
11250
72 302.2 31.2 261.9 216.7 171.5 126.3 - - 288.2 34.2 258.5 213.0 167.4 121.8 - -
67 272.2 30.5 272.2 272.0 238.6 193.5 148.3 - 254.3 33.6 254.3 254.3 234.1 188.5 143.0 -
62 258.2 30.0 258.2 258.2 257.0 211.8 166.6 121.4 236.3 32.8 236.3 236.3 236.3 194.1 147.7 102.1
57 271.1 29.9 271.1 271.1 265.9 220.8 175.6 130.4 254.4 32.8 254.4 254.4 250.0 205.3 158.9 113.3
12500
72 312.8 31.2 283.2 233.4 183.7 133.9 - - 298.6 34.1 279.9 229.6 179.2 128.8 - -
67 281.7 30.6 281.7 281.7 255.6 205.8 156.0 - 263.5 33.5 263.5 263.5 250.6 200.3 149.9 -
62 267.2 30.0 267.2 267.2 267.2 217.4 167.7 117.9 244.9 32.7 244.9 244.9 244.9 194.5 144.2 93.8
57 280.6 29.9 280.6 280.6 280.6 230.9 181.1 131.4 263.6 32.7 263.6 263.6 263.6 213.2 162.9 112.5
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J25YC/J25NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65